Connections; Alerts - KAEL Muhendislik Elektronik VARkombi-12-PC-TFT-OG Manual

Connection type selective, 12 step, reactive power control relay, industrial facilities, markets, oil stations, schools, workshops, hotels
Table of Contents

Advertisement

Connections

Current direction
Alarms
In case of alarm in the device, an exclamation mark appears
under the main screen. Pressing the exclamation key, the alert
page shown on the right side can be displayed on the screen as
well as a warning page can only be displayed. In case of more
than one alert, they are ranked one under the other according to
the priority.
Meanwhile, the phase in which the alarm is given displayed on the
screen. Arrow keys can move between the alarms. In case
"Select" key is pressed during on any alarm (format is blue colour),
warning page of that alert comes to screen. The essential
corrections should be made by taking into consideration the
recommendations made therebefore. Alarm page is back by
pressing the "Exit" key.
C1
*
*
*
K1
K2
*
Fuse compatible
to the capacitor
K3
power
K4
K5
K6
C2
K7
K8
K9
K10
K11
K12
2A
FAN
(Fan output)
2A
ALR
(Alarm output)
CON-2
RS485 - Ethernet
Transformer
Gnd
B
A
TR
k3
I3
k2
connections are shown at
pages 10 and 11.
I2
k1
I1
230Vac
Power
Supply
50/60 Hz
L3 (T)
L2 (S)
connections are shown at
pages 10 and 11
L1 (R)
N
B
A
L3 (T)
L2 (S)
L1 (R)
N
~
1
2 3
4
5 6
7
8 9
10
11 12
18
30
ALARMS
R
S
T
Over voltage
Under voltage
Over current
T. over comp.
Under comp.
Select
Exit
1
2 3
4
5 6
7
8 9
10
11 12
30
Over Voltage
- capacitors and the devices in the system
can be damaged.
- capacitors are recommended to be
disabled.
Exit
4