KAEL Muhendislik Elektronik VARkombi-12-PC-TFT-OG Manual page 31

Connection type selective, 12 step, reactive power control relay, industrial facilities, markets, oil stations, schools, workshops, hotels
Table of Contents

Advertisement

Technical Info
Operating Voltage (Un)
Operating Range
Operating Frequency
Supply Power Consumption
Power Consumption of Measurement Inputs
Contact Current
Current Measurement Range
Display Range
Mimimum Current Measurement Value
Measurement Accuracy
Current Transformer Ratio
Display
RS485
Baud rate
Stop Bits
Parity
Device No
Device Protection Class
Terminal Protection Class
Environment Temperature
Humudity
Device Standart
Connection Type
Dimensions
Installation
1- An outlet in square form by 140 mm x 140 mm will be made on the panel where the assembly of
the device will be made.
2- Prior to the assembly of the device, remove the apparatus of the panel.
3- Insert the device from the front window drilled at the panel.
4- Fix the device to the panel by using panel holding apparatus at the back of the device.
Make the assembly as to leave a 50 mm space between the wall and
the back of the device for ventilation.
PANEL OUTLET MEASUREMENT
:
140mm
: (Phase-Neutral ) 220Vac ; (Phase-Phase) 380 Vac
: (0,8-1,1) x Un
: 50/60 Hz
: < 10VA
: < 1VA
: Max.3A/240 Vac
: (as secondary current of current transformer)
0,01 - 6 Amp AC
: (Power Factor) 0,000 - 1,000 ind.and cap.
: 10 mA
: %1±1 digit
: 5/5..........10000/5 A
: 3,2" coloured LCD
: 2400,4800,9600,19200,28800,38400,57600,115200
: (0.5) , (1) , (1.5) or (2)
: no , even , odd
: 1 .....255
: IP 20
: IP 00
: - 5 °C .... + 50 °C
: %15 ...... %95 (without condensation)
: EN 55011: 2007 + A2 : 2007
EN 61326 : 2006
EN 61000-3-2 : 2006
EN 61000-3-3 : 1995 + A1 : 2001 + A2 : 2005
EN 61010-1 : 2001
: On the front cover of the panel
144x144x45 mm
37 mm
WALL
50mm
28