① Nonincendive field wiring apparatus or intrinsically safe apparatus must be suitable for the ambient
temperature and be wired and separated in accordance with the wiring methods of National Electrical
Code ANSI/NFPA 70, Canadian Electrical Code C22.1 or in accordance with the authority having
jurisdiction.
② Spur connections allow the interconnection of nonincendive field wiring apparatus or intrinsically safe
apparatus with an associated nonincendive field wiring apparatus (Segment Protector) not specifically
examined in combination as a system when V
L
.
cable
③ For nonincendive applications the output voltage of the fieldbus power supply has to be safely limited
according to ANSI/ISA-12.12.01-2013.
current can be switched beween 46 mA and 65 mA (parameters see table "Fieldbus Spur wiring").
④ I
/I
sc
0
WARNING: Ignition hazard - Switch position must be set correctly for the intended gas group as
specified in the Fieldbus Spur Wiring Table.
AVERTISSEMENT : Risque d'inflammation – la position du commutateur doit être correctement réglée
pour le groupe de gaz concerné, comme indiqué dans le tableau de câblage des sorties du bus de
terrain.
⑤ Trunk and spur connectors are only allowed to be manipulated at ambient temperatures between –5 °C
and +70 °C.
⑥ Trunk wiring between the source and the segment protector(s) shall be installed per the Class l,
Division 2 wiring methods specified by the National Electrical Code ANSI/NFPA 70 or Canadian
Electrical Code C22.1.
⑦ Special conditions for safe use:
The use of the Switch is only permitted in the absence of a hazardous atmosphere.
All cables have to be fixed.
The signal lines of any spur must not be connected to earth potential or to the cable shield.
⑧ Usage of the segment protector in FISCO systems:
In combination with the use of a fieldbus power supply with a maximum output voltage of 17.5 V with a
safe output voltage limiting acc. to at least Ex ic the segment protector outputs are rated acc. to the
FISCO model.
Regarding the cable parameters, the cable used for the fieldbus has to be within the following ranges:
-
R' = 15...150 Ohm/km (loop resistance)
-
L' = 0.4...1 mH/km
-
C' = 45...200 nF/km (incl. a possibly existing shield)
-
C' = C'wire/wire + 0.5 * C'wire/shield (with floating field apparatus)
-
C' = C'wire/wire + C'wire/shield (if the shield is connected to one pole of the fieldbus devices
supply circuit)
On each output circuit a maximum cable length of 1 km for group IIC and 5 km for groups IIA, IIB and
IIIC may be connected. If more than one device is connected, the spur cable to each device must be
shorter than 60 m. The maximum cable length must include all spur cables.
⑨ A field terminator shall be mounted at each end of the trunk.
⑩ Spur outputs of the R2-SP-IC* Segment Protector for use in a FISCO ic system require a separation
wall to be mounted on top of the Segment Protector. The separation wall is a mandatory prerequisite to
ensure the required clearance of 50 mm between the trunk terminals and the spur terminals for FISCO
ic.
WARNING: Substitution of components may impair intrinsic safety and suitability for hazardous (classified)
locations.
AVERTISSEMENT : le remplacement des composants peut altérer la sécurité intrinsèque et l'adéquation à
une utilisation dans des zones dangereuses (classées).
WARNING: Explosion Hazard – Do not disconnect incendive circuits while they are live unless area is known
to be non-hazardous.
AVERTISSEMENT: Risque d'explosion - Ne pas débrancher tant que le circuit incendiaire est sous tension,
à moins qu'il ne s'agisse d'un emplacement non dangereux.
Dieses Dokument enthält sicherheitsrelevante Angaben. Es darf nicht ohne Absprache mit dem Normenexperten (NE Ex) geändert werden!
This document contains safety-relevant information. It must not be altered without the authorization of the norm expert (NE Ex) !
CONFIDENTIAL acc. to ISO 16016
Worldwide
or U
max
Only valid as long as released in EDM
Control Drawing
R2-SP-IC*
≥ V
≥ C
or U
; C
or C
i
oc
0
a
o
≥ L
+ C
; L
or L
+
i
cable
a
o
i
date: 2017-Sep-08
116-0406
2
3
sheet
of