Installation - Suburban DYNAPACK S Series Installation, Operating And Service Instructions

Vertical packaged air conditioner featuring gas heat and electric cooling
Hide thumbs Also See for DYNAPACK S Series:
Table of Contents

Advertisement

INSTALLATION

WARNING!
Installation of this appliance must be made in accordance with the written
instructions provided in this manual. No agent, representative or employee of Suburban or
other person has the authority to change, modify or waive any provision of the instructions
contained in this manual.
The Dynapack units are vertical package units featuring gas fired
heating with electrical air conditioning.
safety certified by Intertek Testing Services to comply with the national
safety codes of the USA and Canada. The Dynapack unit is certified to
operate on natural or LP gas.
The Dynapack unit is NOT certified for installation in a mobile
home.
Installations in the USA must be in accordance with city, county, or state
codes and regulations. If local codes do not apply then the installation
must be made in accordance with the National Fuel Gas Code and the
National Electrical Code.
Installations made in Canada likewise must be in accordance with
city, provincial, or national codes or the current version of CANI-B149
Installation Code.
WARNING!
In the state of Massachusetts: This product must be installed by a licensed
Plumber or Gas Fitter. When flexible connectors are used, the maximum length shall not
exceed 36". When lever-type gas shutoffs are used, they shall be T-handle type.
The outdoor fan discharge or the condenser air intake cannot be
connected to field fabricated ducting. This unit can only be installed
using the factory supplied wall sleeves.
LOCATION
IMPORTANT:
The Dynapack condensate drain system is designed to be installed in a
conditioned space. To prevent freezing of the drain condensate in the P-Trap, the installation
location should not be exposed to freezing conditions. In installations where the drain system
is exposed to freezing conditions, we offer an optional heated P-Trap which is available for
purchase. The part number for the heated P-Trap installation kit is K/10348
installation are outlined in Appendix A.
The Dynapack unit is approved for indoor installation only and must
be installed with one of the factory supplied wall sleeves. The unit is
intended to be installed in a closet or equipment room. The unit is
certified for 0" clearance to the cabinet sides, cabinet back and the
first 3 feet of the supply duct. However for accessibility reasons it is
recommended to maintain at least 1" clearance on the sides for proper
installation and servicing. For closet installations allow 4" clearance
from the unit door panels to the closet door. For equipment room
installations allow 24"clearance from the unit door panels to a wall for
servicing.
The wall sleeve and grille is intended to be installed flush with the
exterior wall.
The unit, wall sleeve, and grille are required to be
installed certain distances from adjacent doors, operable windows and
shrubbery. See figure 8.
CAUTION: The unit must be installed level front to back and side to
side. Adjust front leveling legs as necessary.
TOP VIEW
CONTROL WIRES
1" RECOMMENDED
The Dynapack unit has been
and the steps for
4" MIN. TO DOOR
ELECTRICAL POWER
1" RECOMMENDED
Figure 1
WALL SLEEVE AND GRILLE INSTALLATION
Refer to installation instructions included with the wall sleeve kit for
guidance in assembling and installing the wall sleeve and grille.
CAUTION: The sleeve will support the back of the unit.
VENTING
The Dynapack unit uses outside air for combustion and vents the
exhaust products directly outside. The Dynapack unit cannot be vented
with other appliances. The venting system of the Dynapack unit cannot
be modified or adjusted in any manner other than what is specified in
these instructions.
The installation must be planned before hand so that the unit exhaust
vent location complies with local or national codes in regards to
distances between the unit vent and doors, operable windows, side
walks, balconies, and patios. See the National Fuel Gas Code Z223.1
for the USA or Installation Code CANI-B149 for Canada. See Figure 8.
The Dynapack unit contains an adjustable vent. The vent must be adjusted
based on the wall sleeve used for proper operation. See figure 2.
The Dynapack unit venting system is certified to operate at wind speeds
up to 40 miles per hour.
VENT PIPE ADJUSTMENT
The vent pipe must be adjusted to match the depth of the wall sleeve.
CAUTION: Failure to properly adjust the vent can lead to exhaust
recirculation and poor combustion.
1. The vent pipe adjustment is accessible from the condenser air
discharge portion of the unit. The retaining screw for the vent pipe
is located to the right of the condenser fan.
2. Remove and retain the #10 sheet metal screw which attaches the
vent pipe to its mounting bracket. See figure 2.
3. The vent extension tube contains six holes, each of which is
intended for a particular wall sleeve depth. Use table 1 and figure
2 to select the proper mounting hole for the vent extension tube.
4. Reinstall the #10 sheet metal screw to secure the vent extension
tube and exhaust tube to its mounting bracket.
DETERMINING HOLE SETTING
Wall Sleeve Stock
Number
1736 or 1741
1737 or 1742
1738 or 1743
1739 or 1744
1740 or 1745
E
D
C
B
A
2
Approximate Length
Hole #
the Vent Extends from
the Cabinet
A
4
/
inches
3
8
B
6
/
inches
3
8
C
8
/
inches
3
8
D
10
/
inches
3
8
E
12
/
inches
3
8
TABLE 1
SHIPPING POSITION
NOMINAL
POSITION
WALL SLEEVE
DEPTH
A
5 7/8"
B
7 7/8"
C
9 7/8"
D
11 7/8"
E
13 7/8"
Figure 2