Gas Piping; Control Wiring - Suburban DYNAPACK S Series Installation, Operating And Service Instructions

Vertical packaged air conditioner featuring gas heat and electric cooling
Hide thumbs Also See for DYNAPACK S Series:
Table of Contents

Advertisement

INDOOR CFM vs STATIC PRESSURE (Dry coil + no air filter)
Blower
Model Number
0.10" wc
Speed
LO
MED LO
DYPA12AC1A***
MED
MED HI
HI
LO
MED LO
DYPA18AC1A***
MED
MED HI
HI
LO
MED LO
DYPA24AC1A***
MED
MED HI
HI
LO
MED LO
DYPA30AC1A***
MED
MED HI
HI
LO
MED LO
DYPA36AC1A***
MED
MED HI
HI

GAS PIPING

The Dynapack unit has a ½" pipe connection for the gas line. The size
of the gas piping must be based on the length of the run and not the
connection size. See table 5 for reference pipe sizing.
Consult with the local gas utility or code authority for gas piping instal-
lation.
If local codes allow the use of a flexible gas appliance connector,
always use a new listed connector. Do not use a connector which has
previously serviced another gas appliance.
The gas piping should contain a manual shut off valve with test port
near the furnace in addition to a drip leg and a ground joint union for
servicing. The test port needs to be upstream of the manual shut off
valve for leak testing and adjusting the supply pressure regulator.
The manual shut off valve must be rated for the gas piping test pressure.
If not, then the shut off valve must be removed from the piping system
during testing. Once the gas piping up to the shut off valve has been
tested, the remaining piping to the unit gas valve must be tested. Do
not exceed ½ psig or 14" water column for this test or the gas valve may
be damaged.
CAUTION: Suburban does not recommend the use of flex tubing to
make the gas connections to the unit unless the flex tubing is a high
quality stainless certified by CSA and approved for use by local code.
WARNING!
A pipe thread compound resistant to the action of liquefied petroleum (LP)
and natural gas must be used on all pipe joints.
WARNING!
The gas valve supplied with this furnace is rated at 1/2 psig maximum. Any
higher pressure may rupture the pressure regulator diaphragm and may cause over firing
of the burners and improper burner operation. The over firing may result in the creation of
carbon monoxide which could cause asphyxiation.
WARNING! FIRE OR EXPLOSION HAZARD!
exactly could result in serious injury, death, or property damage.
WARNING!
Never test for gas leaks with an open flame. Use a commercially available
soap solution made specifically for the detection of leaks to check all connections. A fire or
explosion may result causing property damage, personal injury, or loss of life.
0.15" wc
0.20" wc
497
473
448
577
562
547
757
748
739
937
920
905
1060
1050
1042
512
491
469
596
568
540
773
761
748
972
955
938
1108
1091
1074
504
483
461
588
560
532
765
753
740
964
947
930
1100
1083
1066
490
465
440
570
540
520
768
755
741
934
922
913
1064
1046
1017
490
465
440
570
540
520
768
755
741
934
922
913
1064
1046
1017
Failure to follow the safety warning
0.25" wc
0.30" wc
0.40" wc
424
400
348
522
497
458
716
692
670
888
872
852
1015
977
927
428
387
320
522
504
447
730
711
675
927
915
874
1057
1039
1002
420
379
312
514
496
439
722
703
667
919
907
866
1049
1031
994
415
385
310
500
476
415
732
704
666
895
873
835
1009
995
965
415
385
310
500
476
415
732
704
666
895
873
835
1009
995
965
TABLE 2

CONTROL WIRING

The room thermostat should be installed on an interior wall and near the
return air for the unit. It is recommended that a 5 conductor thermostat
wire be used in case the room thermostat needs power from the unit
transformer.
The low voltage pigtails for the thermostat wiring must be routed to
the outside of the Dynapack unit for connection. The Dynapack unit
contains a second knockout above the control box for this purpose.
The National Electrical Code requires that low voltage wiring be kept
separate from high voltage wiring and cannot be routed through the
same knockout or conduit. Local codes may also require that an
electrical box be installed on the low voltage knockout to contain the
electrical connections.
Follow the thermostat manufacturers instructions for mounting and
wiring. The low voltage is grounded inside the unit control box. See the
attached wiring diagram on page 8.
1
INLET
" NPT
2
INLET PRESSURE POST.
TEST HOSE GOES OVER
OUTSIDE OF POST.
3
USE
" HEX WRENCH
32
TO OPEN ONE TURN.
4
0.50" wc
0.60" wc
0.70" wc
296
247
212
415
357
317
635
586
558
827
790
728
876
824
758
285
250
213
415
381
324
640
622
586
850
825
796
970
917
868
252
207
N/R
377
320
262
622
572
532
828
782
757
962
922
882
225
170
N/R
365
310
250
621
580
535
800
760
730
935
900
875
225
170
N/R
365
310
250
621
580
535
800
760
730
935
900
875
OUTLET PRESSURE POST.
TEST HOSE GOES OVER
OUTSIDE OF POST. USE
3
" HEX WRENCH TO OPEN
32
ONE TURN.
REGULATOR ADJUSTMENT
BENEATH THIS SCREW COVER
VALVE ON/OFF SWITCH
Figure 5
0.80" wc
160
281
521
677
700
179
291
550
766
796
N/R
202
482
702
827
N/R
205
500
690
828
N/R
205
500
690
828

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents