VENTING/VENT PIPE INSTALLATION

DETERMINING HOLE SETTING
Approximate
Wall Sleeve
Length the Vent
Stock
Hole #
Extends from
Number
the Cabinet
1736 or 1741
A
4-3/8"
B
1737 or 1742
6-3/8"
1738 or 1743
C
8-3/8"
1739 or 1744
D
10-3/8"
E
1740 or 1745
12-3/8"
1769 or 1770
*
14-3/8"
1771 or 1772
*
16-3/8"
*
1773 or 1774
17-3/8"
1821 or 1822
*
18-3/8"
*
1823 or 1824
20-3/8"
*
1825 or 1826
22-3/8"
TABLE 1
* Each exhaust tube is specific to
each sleeve depth.
Suburban DynaPack A&E Manual 07/2019 Rev.6
VENTING
The DynaPack unit uses outside air for combustion and vents the exhaust
products directly outside. The DynaPack unit cannot be vented with other
appliances. The venting system of the DynaPack unit cannot be modified
or adjusted in any manner other than what is specified in these instructions.
The installation must be planned before hand so that the unit exhaust vent
location complies with local or national codes in regards to distances between
the unit vent and doors, operable windows, side walks, balconies, and patios.
See the National Fuel Gas Code Z223.1 for the USA or Installation Code
CANI-B149 for Canada.
The DynaPack unit venting system is certified to operate at wind speeds up to
40 miles per hour.
The DynaPack unit contains an adjustable vent. The vent must be adjusted
based on the wall sleeve used for proper operation.
VENT PIPE ADJUSTMENT FOR S SERIES UNITS
Nominal
The vent pipe must be adjusted to match the depth of the wall sleeve.
Wall
Sleeve
CAUTION: Failure to properly adjust the vent can lead to exhaust
Depth
recirculation and poor combustion.
4"
1. The vent pipe adjustment is accessible from the condenser air
6"
discharge portion of the unit. The retaining screw for the vent pipe
8"
is located to the right of the condenser fan.
10"
2. Remove and retain the #10 sheet metal screw which attaches the
12"
vent pipe to its mounting bracket.
14"
16"
3. The vent extension tube contains six holes, each of which is
17"
intended for a particular wall sleeve depth. Use
18"
proper mounting hole for the vent extension tube.
20"
4. Reinstall the #10 sheet metal screw to secure the vent extension tube
22"
and exhaust tube to its mounting bracket.
FIGURE 3 - S SERIES
See Figure 2.
(continued on next page)
12
See Figure 3.
to select the
Figure 3