39 – 52 MBTU GAS Heat - H Series - 90% + AFUE • • No Outside Condensing Unit • 5-speed ECM Motor • R-410A Refrigerant • Insulated 16 GA Coated Steel Base Pan Ideal For Multi-Family Applications Designed And Built To Perform With Efficient Reliability. Suburban DynaPack A&E Manual 02/2019 Rev.5...
Page 2
This Page Intentionally Left Blank Suburban DynaPack A&E Manual 07/2019 Rev.6...
Suburban is a giant in small space gas heating. We pioneered push button and automatic solid state spark ignitions, and energy-saving DC motors. Suburban dominates the recreational vehicle market with compact heating furnaces, water heaters, and ranges.
Ignition system: solid state Direct Spark Gas connection size 1/2 inch NPT Condensate connection size 3/4 inch NPT Specifications subject to change without notice. Installation must be in accordance with local codes and regulations. Suburban DynaPack A&E Manual 07/2019 Rev.6...
OUTSIDE GRILLE: capacity, and 28 9/16" wide and 32-3/4" tall for units larger than 24,000 BTU in cooling capacity. Special grilles to be supplied by Suburban Manufacturing Company only. Units shall be designed to operate on Natural or LP gas* for the heating cycle.
Direct Spark DYPA30 64-1/2 28-1/8 24-1/2 Gas connection size 1/2 inch NPT Condensate connection size 3/4 inch NPT Specifications subject to change without notice. Installation must be in accordance with local codes and regulations. Suburban DynaPack A&E Manual 07/2019 Rev.6...
OUTSIDE GRILLE: capacity, and 28 9/16" wide and 32-3/4" tall for units larger than 24,000 BTU in cooling capacity. Special grilles to be supplied by Suburban Manufacturing Com- pany only. Units shall be designed to operate on Natural gas for the heating cycle.
See Figure 2. CAUTION: The unit should be installed level front to back and side to side. Adjust front FIGURE 1 leveling legs as necessary. Suburban DynaPack A&E Manual 07/2019 Rev.6 (continued on next page)
Page 11
FIGURE 2 (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
4. Reinstall the #10 sheet metal screw to secure the vent extension tube 1825 or 1826 22-3/8" 22" and exhaust tube to its mounting bracket. TABLE 1 * Each exhaust tube is specific to each sleeve depth. FIGURE 3 - S SERIES (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 13
See Figure 4 unit width vent pipe installation. The vent pipe must terminate WHEN INSTALLED, PIPE SHOULD approximately two inches outside EXTEND PAST GRILLE 2" ± 1/2" the exterior grille. FIGURE 4 FIGURE 5 Suburban DynaPack A&E Manual 07/2019 Rev.6...
See Figure 7. The grille mounting brackets and the outside mounting angles contain small holes for screw engagement. Drill out to a larger size for screw clearance. (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 15
• Double check the level and pitch of the unit from side to side and front to back. Readjust the leg leveler screws if necessary. Tighten the leveling leg jam nut. FIGURE 6 FIGURE 7 (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 16
1826 23-7/8" 24-3/4" 32-5/8" 28-9/16" 32-3/4" DYPA30AC3A WARNING! The unit must be installed with approved wall sleeve and grille accessories for safe operation. Improper installations could result in personal injury, or death. TABLE 2 Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 17
FIGURE 9 (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 18
WALL SLEEVE AND GRILLE INSTALLATION FIGURE 10 FIGURE 11 FIGURE 12 (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 19
-16 JAM NUT WELD NUT ENGAGE FLANGE ON WALL SLEEVE WITH FLANGE ON STRAP. SECURE TO UNIT WITH SELF-DRILLING SCREWS. JAM NUT LEG LEVELER FIGURE 13 FIGURE 15 - H SERIES FIGURE 15 - S SERIES Suburban DynaPack A&E Manual 07/2019 Rev.6...
480 square inches or replaced monthly to keep the cooling coil and interior duct surfaces clean and able to operate most efficiently. Optional TABLE 3 MERV 13 filters are available. (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
If the wall sleeve drain is routed to the building sewer system then it must be trapped to prevent sewer gasses (continued on next page) from escaping. Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 22
S SERIES FIGURE 17 Suburban DynaPack A&E Manual 07/2019 Rev.6...
Follow local codes and standards when designing duct runs to deliver the required airflow. Minimize noise and excessive pressure drops caused by duct aspect ratio changes, bends, dampers and outlet grilles in duct runs. (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 24
The unit is shipped with the Flue Gas Tube Connect the Flue Gas Tube (A) as shown. disconnected Ensure the clamp (shipped in the parts bag) is positioned as shown (B) (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 25
CONNECTION (FIELD SUPPLIED) DRIP LEG (FIELD SUPPLIED) 3/4" X 3/4" X 5/8" TEE DRAIN TRAP TUBE CONDENSATE DRAIN ACCESS PANEL 18" TO COMPRESSOR AND OUTDOOR FAN TRAP ROUTE TO BUILDING DRAIN FRONT VIEW FIGURE 18 Suburban DynaPack A&E Manual 07/2019 Rev.6...
208 volt operation. A disconnect should be installed next to the unit so the electrical power can be turned off for servicing or maintenance. (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
14" water column for this test or the gas valve may be damaged. CAUTION: Suburban does not recommend the use of flex tubing to make the gas connections to the unit unless the flex tubing is a high quality stainless certified by CSA and approved for use by local code.
Page 29
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 PSIG or Less and a Pressure Drop of 0.3 Inch Water Column (Based on a 0.60 Specific Gravity Gas) Suburban DynaPack A&E Manual 07/2019 Rev.6...
12. Once the room reaches the set temperature, the compressor will turn off and the room air blower will turn off 30 seconds later. (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 31
16. If a new blower speed was selected then re-measure the temperature rise and repeat the adjustment if needed. (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 32
Use a R410A saturated temperature chart to calculate the suction super heat. Acceptable values are shown on the chart on the left. See Chart 1. CHART 1 (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 33
BURNERS: The burners can be removed for cleaning or changing orifices. PLEASE NOTE: This service must be performed by a qualified technician. (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
*** Sleeve and grille size contingent only on cooling capacity, not heating capacity. H Series Grille showing hole for exhaust tube. H Series Grille Typical sleeve H Series For both the H and S Series Dynapack units, the grille is designed to fit inside the sleeve. Suburban DynaPack A&E Manual 07/2019 Rev.6...
*** Sleeve and grille size contingent only on cooling capacity, not heating capacity. Typical sleeve S Series Grille S Series For both the H and S Series Dynapack units, the grille is designed to fit inside the sleeve. Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 37
The total heat load added due to ventilation for cooling is 862 + 1300 = 2162 BTU/hr The sensible heat load added due to ventilation for heating is: ‘qvs = Cs x Qv x delta-t = 1.1 BTU/hr*cfm*F x 56 cfm x (68°F-2.2°F) = 4053 BTU/hr. Suburban DynaPack A&E Manual 07/2019 Rev.6...
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE-TO-STATE. Some states do not allow limitations or exclusions, so the above limitations and exclusions may not apply to you. 09/2017 Rev.5 Supersedes 06/2004 (continued on next page) Suburban DynaPack A&E Manual 07/2019 Rev.6...
Page 41
8. Freight charges incurred from parts replacements. 9. Fuel or electricity costs or increases in such costs from any reason whatsoever. 10. Suburban products whose serial number has been altered, defaced or removed. 11. Suburban products installed or warranty claims originating outside the Continental U.S.A., Alaska, Hawaii and Canada.
OF WIRES Please consult the Suburban Manufacturing website at www.SuburbanManufacturing.com for the latest product literature. Detailed dimensional data is available upon request. A complete warranty statement can be found in each product’s Installation/Operation Manual, on our website. As part of the Suburban continuous improvement program, specifications are subject to change without notice.