Suburban DYNAPACK S Series Installation, Operating And Service Instructions page 11

Vertical packaged air conditioner featuring gas heat and electric cooling
Hide thumbs Also See for DYNAPACK S Series:
Table of Contents

Advertisement

The Dynapack condensate drain system is designed to be installed in a conditioned space. To prevent freezing of the drain condensate in the
P-Trap, the installation location should not be exposed to freezing conditions. In installations where the drain system is exposed to freezing
conditions, we offer an optional heated P-Trap which is available for purchase. The part number for the heated P-Trap installation kit is K/10348.
Instructions for installing heated P-Trap kit:
1. Turn power off from main disconnect.
2. Remove existing P-Trap drain.
3. Remove middle & top doors and the control box cover.
4. Slip extruded (black) rubber drain hose back into the unit.
5. Route wires/heat cable on the supplied drain trap through the
bushing for the rubber drain hose.
6. Route wires along existing wires up to Top/Line side of contactor.
7. Wire as per drawing ES48000 sent with the kit to contactor &
ground lug.
NOTE: ROUTE HEAT CABLE IN
HOLE/BUSHING WITH RUBBER
DRAIN TUBE (MAY NEED TO
PUSH DRAIN TUBE BACK OUT
OF THE WAY TO RUN CABLE
THROUGH HOLE) SEE STEP 4 & 8
WIRES/HEAT CABLE
HEATED P-TRAP
WITH BARBED FITTING
MAY NEED TO SLIP ELBOW &
BARBED FITTING OFF P-TRAP
TO INSERT INTO RUBBER HOSE
APPENDIX A
8. Re-insert rubber drain hose through bushing with supplied
9. Insert barbed fitting on the P-Trap into rubber drain hose (soapy
10. Align P-Trap as needed for existing drain plumbing.
11. Use wire ties to secure wires to existing wire/leads.
12. Re-check connections.
13. Replace control box cover, middle & top doors.
14. Unit is ready to be powered on.
SCALE 1 : 2
CONNECT TO EXISTING
DRAIN PLUMBING
APPROX. LOCATION
OF WIRES
11
Wires/Heat cable.
water can be used for easy installation).
(BLACK) RUBBER DRAIN HOSE
DETAIL B
B
STEPS
1.
TU
2.
RE
3.
RE
4.
SLI
5.
RO
BU
6.
RO
7. WIR
8. RE-
WIRE
9. INS
USED
10. A
11. W
12. RE
& TO
UNIT

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents