Starting The Switch - Cisco Nexus 9372PX Hardware Installation Manual

Nx-os-mode switches
Hide thumbs Also See for Nexus 9372PX:
Table of Contents

Advertisement

Installing the Switch Chassis
Step 2
Insert the stripped end of the grounding wire into the open end of the grounding lug, and use a crimping tool to crimp
the lug to the wire (see Callout 2 in the following figure). Verify that the ground wire is securely attached to the grounding
lug by attempting to pull the wire out of the crimped lug.
Figure 8: Grounding the Chassis
1
Chassis grounding pad
2
Grounding cable, with 0.75 in. (19 mm) of insulation
stripped from one end, inserted into the grounding
lug and crimped in place
Step 3
Secure the grounding lug to the chassis grounding pad with two M4 screws (see Callouts 1 and 3 in the previous figure),
and tighten the screws to 11 to 15 in-lb (1.24 to 1.69 N·m) of torque.
Step 4
Prepare the other end of the grounding wire and connect it to an appropriate grounding point in your site to ensure an
adequate earth ground for the switch. If the rack is fully bonded and grounded, connect the grounding wire as explained
in the documentation provided by the vendor for the rack.

Starting the Switch

You start the switch by connecting it to its dedicated power source. If you need n+1 redundancy, you must
connect each of the power supplies to one or two power sources. If you need n+n redundancy, you must
connect each power supply in a switch to a different power source.
Before You Begin
• The switch must be installed and secured to a rack or cabinet.
3
Cisco Nexus 9372PX and 9372PX-E NX-OS-Mode Switches Hardware Installation Guide
Two M4 screws used to secure the grounding lug to
the chassis

Starting the Switch

21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nexus 9372px-e

Table of Contents