Installing the Chassis
1
Chassis grounding pad
2
Grounding cable, with 0.75 in. (19 mm) of insulation
that is stripped from one end, which is inserted into
the grounding lug and crimped in place
Step 3
Secure the grounding lug to the chassis grounding pad with two M4 screws, see the previous figure. Tighten the screws
to 11 to 15 in-lb (1.24 to 1.69 N·m) of torque.
Step 4
Prepare the other end of the grounding wire and connect it to the facility ground.

Starting the Switch

You start the switch by connecting it to its dedicated power source. If you need n+1 redundancy, you must
connect each of the power supplies to one or two power sources. If you need n+n redundancy, you must
connect each power supply in a switch to a different power source.
Note
Before you begin
• The switch must be installed and secured to a rack or cabinet.
• The switch must be adequately grounded.
• The rack must be close enough to the dedicated power source so that you can connect the switch to the
• You have the designated power cables for the power supplies that you are connecting to the dedicated
This equipment is designed to boot up in less than 30 minutes, dependent on its neighboring devices being
fully up and running.
power source by using a designated power cables.
power sources.
Cisco Nexus 93400LD-H1 NX-OS Mode Switch Hardware Installation Guide
3
2 M4 screws are used to secure the grounding lug to
the chassis
Starting the Switch
21