Unit Description
The CVGF units are singlecompressor, gear-type, watercooled liquid chillers designed
for installation indoors. Each unit is a completely assembled, hermetic package that is
factorypiped, wired, leak-tested, dehydrated, oil-charged, and tested for proper control
operation before shipment.
Note: high-voltage starters are not unit-mounted before shipment.
Figure 2 and Figure 3 show a typical CVGF unit and its components. Water inlet and
outlet openings are covered before shipment. The oil tank is factory-charged with 15
gallons (56.8L) of Trane Oil 37 and a holding charge of 5 psig (34 kPa) of dry nitrogen at
70°F (21°C).