Installation: Mechanical
Thermal Insulation
All CVGF units are available with optional factory installed thermal insulation. If the
unit is not factory insulated, install insulation over the areas with designated dotted
lines in Figure 25. Refer to Table 17 for types and quantities of insulation required. All
CVGF units come from the factory with oil sump insulation.
Notes: Refrigerant charging valves, water temperature sensors, and drain and vent
connections, when insulated, must remain accessible for service.
Use only water-base latex paint on factory applied insulation. Failure to do so may re-
sult in insulation shrinkage.
Note: Units in environments with higher humidity may require additional insulation.