Condensate Drainage; Anti-Vibration - Trane CGCN Installation Operation & Maintenance

Indoor air-cooled chillers and heat pumps
Table of Contents

Advertisement

Condensate drainage

It is critical to easily discharge condensate caused by the heat pump operation, especially during the defrosting
cycle. Avoid placing the condensate drain where people transit.

Anti-vibration

Isolation rubber pads are supplied as standard with the unit, and should be placed between the supporting floor
and the unit to isolate the base from the ground.
Secure the bottom part of the anti-vibration to the base
unit will support it. (fix the anti-vibration bolts)
Screw nut and lock nut to adjust the proper leveling of the
unit . The units positioned incorrectly can cause damage
to the compressor to incorrect leveling of the oil.