Trane CGCN Installation Operation & Maintenance page 14

Indoor air-cooled chillers and heat pumps
Table of Contents

Advertisement

Connection diagram
No.
Conn.
Designation
KL1
1
L1
KL1
2
L2
KL1
3
L3
PE
1
PE
KL2
1
RSA
KL2
2
RSB
KL2
3
GND
KL2
4
C
KL2
5
Din1
KL2
6
+10V
KL2
7
Ain1U
KL2
8
NC
Function/assignment
Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz
Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz
Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz
Ground connection, PE connection
Bus connection RS485, RSA, MODBUS-RTU; SELV
Bus connection RS485, RSB, MODBUS-RTU; SELV
Reference ground for control interface; SELV
Status relay, floating status contact, break for failure; contact rating 250
VAC / max. 2 A (AC1) / min. 10 mA
Digital input 1 enable electronics,
enable: pin open or applied voltage 5-50 VDC
Din16KL2disable: bridge to G7ND or applied voltage < 18 VDC
reset function: triggers software reset after a level change to < 1 V;
SELV
Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-
proof, power supply for external devices (e.g. pot); SELV
Or: +24 VDC input for parameter setting via MODBUS without line
voltage
Analog input 1 (set value) 0-10 V, Ri = 100 kΩ, adjustable curve; SELV
Status relay, floating status contact, break for failure