Trane CGCN Installation Operation & Maintenance page 36

Indoor air-cooled chillers and heat pumps
Table of Contents

Advertisement

SPOTTED PRESENCE OF MOLD, MUSHROOMS, BACTERIA, MICROBIAL OF ANY TYPE.
THE UNIT DISPLAYS DAMAGES CAUSED BY: FLOODS, LIGHTNING, FIRE, ANY ACCIDENT BEYOND
TRANE'S CONTROL.
ELECTRIC AND ELECTRONIC
THE UNIT IS ELECTRICALLY POWERED AND ALL THE RELEVANT ELECTRICAL WIRES ARE PROPERLY
CONNECTED.
ELECTRICAL SUPPLY HAS BEEN INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS PROVIDED
IN THE NAME PLATE AND IN THE TECHNICAL DOCUMENTATION. (ELECTRICAL POWER SUPPLY:
230V/400V +/- 10% - MAXIMUM "%" OF PHASE IMBALANCE: +/- 3% ) . IT IS RECOMMENDABLE TO
CHECK BY USING A TESTER THE VOLTAGE VALUE ( BETWEEN PHASES AND BETWEEN PHASE AND
NEUTRAL)
PHASES ARE CONNECTED IN THE PROPER SEQUENCE.
ELECTRICAL CABLES SIZE CONFORMS TO FLA MAX VALUE.
BOTH EXTERNAL AND INTERNAL ELECTRICAL WIRES ARE WELL TIGHTENED.
THE COMPRESSOR CRANKCASE HEATERS HAVE BEEN POWERED AND HEATED AT LEAST 8 HOURS
BEFORE THE START-UP.
AN ELECTRONIC SUPERVISOR (OR ANY ADDITIONAL CONTROLLER) HAS BEEN INSTALLED.
CONNECTION WIRES ARE SHIELDED.
REMOTE CONTROL DEVICES OR INTERFACES ARE CONNECTED TO THE ELECTRICAL PANEL IN
CONFORMITY WITH TRANE WIRING DIAGRAMS.
ELECTRIC DEVICES ARE INTACT AND DON'T DISPLAY ANY DAMAGE.
ELECTRONIC DEVICES ARE INTACT AND DON'T DISPLAY ANY DAMAGE.
WATER PUMPS ARE ELECTRICALLY CONNECTED TO THE ELECTRICAL PANEL IN ACCORDANCE
WITH THE WIRING DIAGRAMS PROVIDEDBY TRANE.
THE ELECTRICAL ABSORBTION AND THE WATER PUMPS OVERHEATING ARE STANDARD.
REFRIGERANT CIRCUIT
ALL CONNECTIONS ON THE REFRIGERANT CIRCUITS ARE WELL TIGHTENED.
THE ELECTRONIC LEAKAGE DETECTOR OR THE PRESSURE GAUGE LEVEL INSTALLED ON THE REFRI-
GERANTCIRCUIT HAVE DETECTED ANY LEAKAGE.
IF ANY, SPECIFY BELOW: