Free Vent Flame Arrestor
Specifications
The Specifications section lists the specifications for the Free Vent Flame Arrestors. The following information is stamped on the nameplate attached
to the arrestor: model number, flange size and rating, maximum initial operating pressure, EN number (European Standard), EC type examination
certificate, notified body number, gas group, date of manufacture and serial number; other identification and customer tag number are optional.
Available Constructions
See Table 1 and Figure 2
Gas Group
IIA and IIB3
Flange Sizes and Rating
2 to 12 inches / 50 to 300 mm
CL150 RF and CL150 FF
Housing Size
4 to 24 inches / 100 to 600 mm
Operational Temperature (T
140°F / 60°C
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
EN
Housing
Connection
Size
Size
04 = 4 inches
01 = 1 inch
through
through
24 = 24 inches
12 = 12 inches
Figure 2. Free Vent Flame Arrestor Available Constructions and Model Numbering System
MODEL
EN-FVFA-0402
EN-FVFA-0603
EN-FVFA-0803
EN-FVFA-0804
EN-FVFA-1206
EN-FVFA-1608
EN-FVFA-2010
EN-FVFA-2412
Hastelloy
is a mark owned by Haynes International, Inc.
®
2
)
(1)
o
/
-
IEC
Housing
Gas
Material
Group
IIA
C = Carbon Steel
IIB3
4 = 304 SST
6 = 316 SST
H = Hastelloy
®
Table 1. EN FVFA Series Available Construction
FLANGE SIZE
Inch
2
3
3
4
6
8
10
12
Burning Time Rating
Less than 1 minute
Housing Material
Carbon steel, 304 Stainless steel,
316 Stainless steel and Hastelloy
Element Material
304 Stainless steel, 316 Stainless steel
and Hastelloy
®
EN Number (European Standard)
EN ISO-16852
Element
Connection
Material
Type
4 = 304 SST
F = Flat face
6 = 316 SST
flange
H = Hastelloy
®
R = Raised
face
flange
mm
Inch
50
4
75
6
75
8
100
8
150
12
200
16
250
20
300
24
®
-
FVFA
Options
2 = Pressure Tap
3 = Temperature Probe Tap
4 = Miscellaneous
5 = Protective coating
6 = Special feature
HOUSING SIZE
mm
100
150
200
200
300
400
500
600