Assembly, Disassembly and Electrical Installation
10.8.2 Connecting the Control Cabinet PC to Operating Display
Connection diagram
Operator display
Functional earth ground
Fig. 10-24: Wiring the operating display to the control cabinet PC
Connection
1. Connect the functional earth ground.
2. Connect the violet RJ45 data interface "XSER" at the operating display to
the RJ45 data interface "XSER" at the control cabinet PC.
3. Connect the black RJ45 image data interface "XVID" at the operating dis-
play to the RJ45 image data interface "XVID" at the control cabinet PC.
NOTICE
Ensure that the functional earth ground is connected, as otherwise the electron-
ics can be destroyed by a potential difference between the VDP and the PC if
the voltage supply is interrupted to only one device and re-established. A direct
connection of the functional earth ground between the VDP xx.3 display and
control cabinet PC is optimal. If the functional earth ground is connected to a
neutral point, the control cabinet PC has to be connected to this neutral point.
34/53
Violet
XSER
XVID
Black
Material damages to electronics due to missing
functional earth ground connection!
VDP 16.3, VDP 40.3, VDP 60.3
XSER
Control cabinet PC
XVID