Connect only USB devices that meet the USB specification.
NOTICE
The max. power consumption of one USB connector must not exceed 500 mA.
The total current of all USB female connectors must not exceed 1 A.

9.6 XSER Interfaces and XVID Interfaces

CDI interface
The CDI interface is assigned to the two RJ45 female connectors XSER and
XVID. The connection between the control cabinet PC and the operating display
is established on these female connectors via two ready-made cables available
as accessory, see
chapter 5 "Spare Parts, Accessories and Wear Parts" on page
6.
The CDI interface includes the data interface (XSER) as well as the screen inter-
face (XVID).
XVID and XSER Markings
The CDI interfaces are color-coded on the device:
CDI interface, data (XSER)
CDI interface, screen (XVID)
Tab. 9-4: Color-coding of the interface
10 Assembly, Disassembly and Electrical Installation

10.1 Installation Notes

Provide a space of 50 mm on all sides of the device for sufficient cooling and
cable routing
The LED displays on the connector must not be covered
Lay all cable in loops. Use strain reliefs for all cables
Keep as much distance as possible to noise sources
Only install the operating display vertically, with a max. deviation of ±45°,
measured from the vertical
Do not lay the CDI cables in parallel to motor cables or to other noise sources
as otherwise the CDI connection may be disturbed
16/53
VDP 16.3, VDP 40.3, VDP 60.3
The VDP power supply switches off if the total
current of all USB connectors exceeds 1 A.
Violet
Black
DOK-SUPPL*-VDP*XX.3***-IT03-EN-P

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Indracontrol vdp 60.3Indracontrol vdp 40.3

Table of Contents