Initial Inspection; Burner Service Procedure; Boiler Service Procedure - Hamworthy LILIPUT HE Installation, Commisioning And Maintenance Instructions

Gas/oil fired cast iron sectional boilers
Table of Contents

Advertisement

s.
Check all cleaning door, burner mounting and
flue hood joints for flue gas leakage and
tighten all fixings.
t.
Set boiler control thermostat to required
setting, and check operation of heating
control system.
u.
Fully familiarise the user with the boiler
operating controls, the main component
functions and the safety features.
THESE
INSTALLATION
INSTRUCTIONS SHOULD BE LEFT WITH THE
USERS OF THE BOILER FOR THEIR FUTURE
REFERENCE.
9.
SERVICING
The boiler should be serviced by a competent
person.
The Gas Safety (Installation and Use)
Regulations require that only Registered (i.e.
CORGI Registered) gas personnel should install,
commission and service gas fired equipment such
as these boilers. Failure to comply with these
Regulations may lead to prosecution.
The boiler should be serviced at regular intervals,
not exceeding SIX months for oil fired boilers, or
TWELVE months for gas fired boilers.
When carrying out boiler servicing always consider
both your own safety and that of others. The use of
protective equipment (e.g. eye protection, face
mask, protective gloves, etc.) is recommended
where necessary.
9.1

Initial Inspection

a.
a.
Operate boiler and check for any signs
of unsatisfactory operation, water leaks, gas
leaks, oil leaks or unusual noise from burner
oil pump or motor.
b.
b.
After allowing burner to reach stable
firing conditions for approximately 15 minutes,
carry out combustion gas check.
c.
Measure
temperature, smoke number (for oil) and
water temperature rise across the boiler. The
readings obtained should be as given in
Section 8 - Commissioning.
d.
c.
Measure either gas pressure at burner
head, or oil pressure at burner pump, as
applicable, and check value is correct for size
of boiler in question.
e.
d.
Check operation of both boiler and
heating system controls, then set boiler
control thermostat to OFF.
9.2

Burner Service Procedure.

SWITCH OFF ELECTRICAL SUPPLY TO BOILER
AT ISOLATOR AND SHUT OFF FUEL SUPPLY
TO BOILER.
HAMWORTHY HEATING LTD
AND
SERVICING
CO
,
CO,
flue
2
a.
a.
storage tank and examine for leaks and signs
of deterioration.
b.
and clean or recommend replacement as
necessary.
c.
b.
connections to burner, as necessary.
d.
of
hardening of inner tube.
e.
c.
flange and remove from front of boiler.
f.
d.
check photocell is clean, check electrode rod
contacts, check wires in base of control box
and condition of electrical spring connectors.
Wipe nozzle clean and inspect for spark
erosion.
g.
e.
thoroughly. Check combustion head settings
are correct, as specified in the manufacturer's
technical information supplied with the burner.
Check diffuser disc slots are clean.
h.
f.
inspecting for any signs of deterioration or
crazing in porcelain.
i.
in the manufacturer's technical information
supplied with the burner.
9.3

Boiler Service Procedure

a.
a.
casing to gain access to front of boiler.
b.
b.
side of the front door of the boiler. Swing it
open to gain access to the boiler combustion
chamber and heat exchanger flueways and
thoroughly clean using a suitable brush(es)
and a vacuum cleaner.
c.
c.
gas
flueways and combustion chamber can be
obtained by removing flue box, cover plate
and insulation panels from rear of boiler.
Check condition of all insulation and replace if
necessary.
d.
N.B. Removal of the rear cover plate and flue
box requires disconnection of flue.
e.
d.
ensuring that ceramic rope seal is both sound
and correctly positioned. Evenly tighten the
two nuts on the non-hinge side to secure the
door.
f.
e.
to Section 7.
g.
f.
electrical supplies.
h.
g.
soundness of fuel supply pipework.
15
LILLIPUT HE
For oil installations: Desludge oil
Examine contents gauge for visibility
Disconnect
electrical
Examine flexible oil line(s) for any signs
deterioration,
leakage,
Disconnect
burner
For oil burners: Remove control box,
Remove burner blast tube and clean
Remove, clean, and check electrodes
Check electrode gaps are as specified
After removing burner, remove boiler
Slacken the two nuts on the non hinge
Access to rear of heat exchanger
After cleaning, close front door of boiler
Refit boiler casing. For guidance, refer
Refit burner.
Reconnect fuel and
Turn
on
fuel
supply
and
fuel
damage,
or
from
mounting
and
check
500001047/F