Electromagnetic Flowmeter
WaterMaster

4.7.3 Configuration DIP Switches

Three configuration DIP switches are mounted on the transmitter backplane board.
These are factory set as follows:
Remote transmitter – all OFF
Integral transmitter – SW3 ON
For MID-compliant flowmeters set the read-only / MID protection switch to 'ON' to ensure the meter is
secure from tampering. For software versions prior to 01.02.XX, this switch, set after commissioning,
prevents login via the keypad or bus, at any security level. From software version 01.03.XX onwards, on
MID meters, all metrological-related parameters are locked and inaccessible at the service level. Standard
and advanced user level parameters can still be modified via the HMI or bus.
Fig. 4.19 Configuration DIP Switches
30
Configuration
DIP Switches
OFF
ON
SW3 SW2 SW1
4 Electrical Installation
DIP Switch Functions
SW1 – Read-only / MID Protection
SW2 – (Future Product)
SW3 – Internal Sensor Memory