Page 1
INSTRUCTION MANUAL VARIABLE PERCENTAGE DIFFERENTIAL RELAY BE1-87G SWITCH POSITION AMPS 0.02 0.03 0.04 0.08 0.16 0.32 POWER BE1-87G GENERATOR DIFFERENTIAL RELAY Style No. G2E A1J A0C0F Serial No. H123456789101 PUSH TO ENERGIZE OUTPUT CAUTION: UPPER CONNECTION PLUG MUST BE IN PLACE PRIOR TO INSERTING OR REMOVING LOWER CONNECTION PLUG.
Page 3
NOTE Be sure that the BE1-87G is hard-wired to earth ground with no smaller than 12 AWG copper wire attached to the ground terminal on the rear of the unit case. When the BE1-87G is configured in a system with other devices, it is recommended to use a separate lead to the ground bus from each unit.
Page 4
United States and/or other countries. CONFIDENTIAL INFORMATION of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject to return on request, and with the mutual understanding that it will not be used in any manner detrimental to the interest of Basler Electric.
Page 5
REVISION HISTORY The following information provides a historical summary of the changes made to the BE1-87G instruction manual (9170800990). Revisions are listed in reverse chronological order. Manual Revision and Date Change M, 03/10 Changed the sensing input range specifications for pickup accuracy in Section 1.
Page 6
Changed operational test procedure in Section 5. A, 05/86 Added qualifications to specifications of Section 1. Revised isolation test and dielectric test information in specifications of Section 1. —, 12/85 Initial release BE1-87G Introduction 9170800990 Rev M...
Page 7
SECTION 1 ● GENERAL INFORMATION ....................1-1 SECTION 2 ● CONTROLS AND INDICATORS ..................2-1 SECTION 3 ● FUNCTIONAL DESCRIPTION ................... 3-1 SECTION 4 ● INSTALLATION ........................4-1 SECTION 5 ● TESTING AND SETTING ....................5-1 9170800990 Rev M BE1-87G Introduction...
Page 8
This page intentionally left blank. BE1-87G Introduction 9170800990 Rev M...
87G provides a restraint factor that is proportional to input current when the restraining current (I ) is greater than nominal (5 Aac for sensing input range 1 or 1 Aac for sensing input range 2). The BE1-87G compares the protected zone sensed input and output currents. The lesser of the two sensed current levels becomes the restraining current.
Figure 1-3. Style Number Identification Chart SPECIFICATIONS BE1-87G relays have the following features and capabilities. Current Sensing Inputs Sensing Input Range 1 Nominal Rating: 5 Aac Maximum Continuous Rating: 10 Aac 1 Second Rating: 250 Aac Frequency Range: 45 to 65 Hz <0.05 Ω...
230 Vac 90 to 270 Vac 9.20 VA ∗ The type L power supply initially requires 14 Vdc to begin operating. Once operating, the voltage may be reduced to 12 Vdc and operation will continue. 9170800990 Rev M BE1-87G General Information...
Single-Phase Sensing Units: 14.3 lb (6.5 kg) maximum Three-Phase Sensing Units: 19.2 lb (8.7 kg) maximum Case Size All units are supplied in an S1 case size. See Section 4, Installation for case dimensions. BE1-87G General Information 9170800990 Rev M...
UL Recognition: UL recognized per Standard 508, File E97033 NOTE: Output contacts are not UL recognized for voltages greater than 250 volts. GOST-R Certification GOST-R certified per the relevant standards of Gosstandart of Russia. 9170800990 Rev M BE1-87G General Information...
Page 18
This page intentionally left blank. BE1-87G General Information 9170800990 Rev M...
SECTION 2 ● CONTROLS AND INDICATORS TABLE OF CONTENTS SECTION 2 ● CONTROLS AND INDICATORS ..................2-1 GENERAL .............................. 2-1 Figures Figure 2-1. Controls and Indicators ......................2-1 Tables Table 2-1. Control and Indicator Descriptions ................... 2-1 9170800990 Rev M BE1-87G Controls and Indicators...
Page 20
This page intentionally left blank. BE1-87G Controls and Indicators 9170800990 Rev M...
Page 21
SECTION 2 ● CONTROLS AND INDICATORS GENERAL BE1-87G controls and indicators are illustrated in Figure 2-1 and described in Table 2-1. Figure 2-1. Controls and Indicators Table 2-1. Control and Indicator Descriptions Locator Description Sensitivity Switch. This thumbwheel switch has seven positions labeled A through G and sets the desired level of operating current that will cause the relay to trip.
Page 22
This page intentionally left blank. BE1-87G Controls and Indicators 9170800990 Rev M...
Sensing current for each monitored phase is provided by two user-provided, system CTs with secondary windings that match the BE1-87G’s sensing input range. BE1-87G relays with sensing input range 1 (style x1x-xxx-xxxx) require CTs with 5 Aac secondary windings. Relays with sensing input range 2 (style x2x- xxx-xxxx) require CTs with 1 Aac secondary windings.
(I ). The restraint current is scaled for a 50% slope above nominal input current (5 Aac for sensing input range 1 or 1 Aac for sensing input range 2). BE1-87G Functional Description 9170800990 Rev M...
The main output relay contacts are either normally-open or normally-closed and are accessed at case terminals 1 and 10. Normally-open contacts are provided on BE1-87G relays with a style number of xxE- xxx-xxxxx and normally-closed contacts are provided on relays with a style number of xxG-xxx-xxxxx.
A front panel LED power indicator lights to indicate that the power supply is functioning properly. Style number designations and input voltage ranges for the available power supply models are provided in Section 1, General Information. BE1-87G Functional Description 9170800990 Rev M...
Page 30
This page intentionally left blank. BE1-87G Installation 9170800990 Rev M...
Page 31
If there is any evidence of shipping damage, file a claim with the carrier and notify Basler Electric. If the relay won’t be installed immediately, store it in its original shipping carton in a moisture- and dust- free environment.
Page 32
Figure 4-1. Panel Cutting and Drilling Dimensions, Semi-Flush Mounting, Double- or Single-Ended Case BE1-87G Installation 9170800990 Rev M...
Page 33
Figure 4-2. Panel Drilling Dimensions, Projection Mounting, Double-Ended Case 9170800990 Rev M BE1-87G Installation...
Page 35
D2853-22 06-15-99 Figure 4-4. Outline Dimensions, Side View, Semi-Flush Mounted, Double-Ended Case 9170800990 Rev M BE1-87G Installation...
Page 36
D2853-23 06-15-99 Figure 4-5. Outline Dimensions, Side View, Semi-Flush Mounted, Single-Ended Case BE1-87G Installation 9170800990 Rev M...
Page 37
Figure 4-6. Outline Dimensions, Side View, Projection Mounted, Double-Ended Case 9170800990 Rev M BE1-87G Installation...
Page 38
CASE DETAIL A-A SHOWING THE ADDITION OF WASHERS OVER THE BOSS TO TIGHTEN THE RELAY AGAINST THE PANEL. P0002-18 12-07-01 Figure 4-7. Outline Dimensions, Side View, Projection Mounted, Single-Ended Case BE1-87G Installation 9170800990 Rev M...
Page 39
Figure 4-8. Outline Dimensions, Rear View, Double-Ended Mounting Case 9170800990 Rev M BE1-87G Installation...
Page 41
Figure 4-10. Outline Dimensions, Front View, Case Cover 9170800990 Rev M BE1-87G Installation 4-11...
Page 42
Figure 4-11. Overall Dimensions, Stabilizing Reactor Figure 4-12. Outline Dimensions, Side View, Semi-Flush Mounted Case with Attached Stabilizing Reactor 4-12 BE1-87G Installation 9170800990 Rev M...
Page 43
Typical sensing current connections for a single-phase application are shown in Figure 4-16. Three-phase sensing current connections are illustrated in Figures 4-17 and 4-18. Figure 4-17 shows the sensing inputs connected in a wye configuration. Figure 4-18 shows the sensing inputs connected in a delta configuration. 9170800990 Rev M BE1-87G Installation 4-13...
Page 50
MAINTENANCE BE1-87G relays require no preventive maintenance other than the periodic inspection of the relay case and stabilizing reactor terminal connections to ensure that they are clean and tight. If repairs are needed, contact the Technical Sales Support department at Basler Electric for assistance.
The relay case must be hard-wired to earth ground with no smaller than 12 AWG copper wire. A separate ground lead is recommended for each device. OPERATIONAL TEST PROCEDURE The procedures that follow verify proper operation of the BE1-87G relay CAUTION During testing, do not apply a continuous operate current greater than 3 Aac.
Figure 5-1. Location of Stabilizing Reactor Bypass Terminals (Single-Phase Relays) Equipment Required Because of the speed and sensitivity of the BE1-87G, test equipment with appropriate accuracy and stability must be used to test the sensitivity switch settings. For example, at the most sensitive switch setting (0.1 ampere), the relay monitors a current difference that is only 1% for a sensing input of 10...
Perform the following steps to test the trip and dropout accuracy of phases B and C of relays with three- phase sensing (style number Gxx-xxx-xxxxx). Perform steps 1 through 7 under Single-Phase/A-Phase Trip and Dropout Test for phases B and C. 9170800990 Rev M BE1-87G Testing and Setting...
I” Sub-transient current Total number of CT turns Number of CT turns in use (for multi-ratio type) One-way lead resistance in ohms Relay restraint circuit resistance in ohms CT winding resistance in ohms 9170800990 Rev M BE1-87G Testing and Setting...
Inequality (1) is met with CT #2, but not with CT #1. However, since the locked rotor current is only 4.8 times the CT rating (versus the assumption of 20 times rated for inequality (1)), the application is suitable. SFR = (100 ÷ 50) × (0.36 ÷ 0.19) = 3.8 BE1-87G Testing and Setting 9170800990 Rev M...
CT #2 has a C classification. The T classification indicates that the CT has significant secondary leakage inductance which somewhat degrades the transient performance. This is a concern during motor starting because a slowly decaying offset component develops in at least one phase. 9170800990 Rev M BE1-87G Testing and Setting...