Cisco UCS 6332 Hardware Installation Manual page 38

Fabric interconnect
Table of Contents

Advertisement

Wiring a DC Power Connector
In a system with dual power supplies, connect each power supply to a separate power source. In case of a
power source failure, the second source will most likely still be available.
Step 6
Verify power supply operation by checking that the power supply LED is green.
Wiring a DC Power Connector
Warning
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. Statement 1022
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building installation.
Install only in accordance with national and local wiring regulations. Statement 1045
Warning
When installing or replacing the unit, the ground connection must always be made first and disconnected last.
Statement 1046
Warning
Installation of the equipment must comply with local and national electrical codes. Statement 1074
Warning
Hazardous voltage or energy may be present on DC power terminals. Always replace cover when terminals
are not in service. Be sure uninsulated conductors are not accessible when cover is in place. Statement 1075
Before installing a DC power supply to the fabric interconnect, you must attach DC connection wires that
you provide (10 GA recommended) to the DC power connector included in the DC power supply's accessory
kit.
Procedure
Step 1
Using a 1/8-inch flat head screwdriver or No. 1 Phillips head screwdriver, loosen the set screws on the connector
to freely accept the power wires. The connector will accept 8-24 AWG wires. Use what your local electrical
code requires.
Step 2
Strip 1/2-inch of insulation off the DC wires you will use.
Step 3
Insert the black (DC negative) wire into the right aperture on the connector and tighten down the connection
set screw. Finger tight or about 3 ft./lbs should be sufficient.
Step 4
Insert the red (DC positive) wire into the left aperture on the connector and tighten down the connection set
screw. Do not tighten over 0.51 ft./lbs.