DI setting
Click IO setting to enter I/O setting page, then select Digital tab to configure DI
channels.
Powering and Insulation
Parameters
Channel
Input type
Wet Contact Input
Rated Voltage
Rated Input Current
Over Voltage Protection
Isolation Voltage
DI could be configured as Pulse meter or Open/Close contact.
Pulse meter: measuring value will
Open/Close contact
in status 0 and status 1.
Fig. 16
Parameters
Parameters
Name
Input type
Unit
Pulse weight
Status 0
Status 1
2TFP900034A1001 ECN000087106 Rev. A
:
digital value 0 and 1 will be transferred into meaningful words set
Description
DI channel name
DI input types for this channel:
Pulse meter
Open/Close contact
Unit for the measurement
Increment for Pulse meter.
For Open/Close contact type: Meaning of status
0
For Open/Close contact type: Meaning of status
1
NOTE: Please configure the DI channels according to the real environment. The
DI channels' data will be upload to the cloud after finishing the provision
process. If there is type changing in the DI channel, please do a re-provisioning
process to make the changes valid.
Description
8 Channels
Sink (Wet Contact)/Counter
Logic 0: 0 ~ 5 VDC
Logic 1: 11 ~ 30 VDC
12/ 24 VDC
> 5mA@ 12VDC
> 10mA@ 24VDC
+40VDC
2000VDC
be increased one weight at each pulse
Default
DI Channel No.
Pulse meter
N/A
0.1
Status 0
Status 1
Ekip E-Hub | 21