Bryant 581J-04A Installation Instructions Manual page 32

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for 581J-04A:
Table of Contents

Advertisement

Table 16 — Dry Bulb Operation With DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
Below CO
Set
2
Above CO
Set
2
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and
Y2-I have not been satisfied.
Table 17 — Enthalpy Operation No DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
NO CO
SENSOR
2
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and
Y2-I have not been satisfied.
Table 18 — Enthalpy Operation With DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
Below CO
Set
2
Above CO
Set
2
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and
Y2-I have not been satisfied.
Y1-I
Y2-I
SPEED
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
ON
OFF
Yes
ON
ON
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
Yes
ON
OFF
ON
ON
Y1-I
Y2-I
SPEED
OFF
OFF
NO
ON
OFF
ON
ON
OFF
OFF
ON
OFF
YES
ON
ON
Y1-I
Y2-I
SPEED
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
ON
OFF
Yes
ON
ON
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
Yes
ON
OFF
ON
ON
Sensor) — 2 Speed Fan
2
FAN
Y1-O
Y2-O
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off*
Sensor) — 2 Speed Fan
2
FAN
Y1-O
Y2-O
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off*
Sensor) — 2 Speed Fan
2
FAN
Y1-O
Y2-O
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off*
32
OCCUPIED
UNOCCUPIED
VENTMIN
Closed
VENTMIN
Closed
VENTMIN
Closed
VENTMIN
Closed
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed
VENTMAX
VENTMIN to
Closed
VENTMAX
VENTMIN to
Closed
VENTMAX
VENTMIN to
Closed
VENTMAX
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
OCCUPIED
UNOCCUPIED
MIN POS
Closed
MIN POS
Closed
MIN POS
Closed
MIN POS
Closed
MIN POS to Full
Closed to Full-Open
Open
MIN POS to Full
Closed to Full-Open
Open
OCCUPIED
UNOCCUPIED
VENTMIN
Closed
VENTMIN
Closed
VENTMIN
Closed
VENTMIN
Closed
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed
VENTMAX
VENTMIN to
Closed
VENTMAX
VENTMIN to
Closed
VENTMAX
VENTMIN to
Closed
VENTMAX
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open