10. TROUBLESHOOTING GUIDE

10.1 Not cool at all [ Both PC & FC (compressor does not operate) ]
1
Does room light turn on?
Pushing PC door switch and room light turns
2
off, and after release PC door switch, does
room light turn on?
To start self diagnosing function by opening
3
PC door and FC door and pushing
"Quick Freezing" SW for 5 seconds.
Does "ECONAVI Led" and "Quick Freezing"
4
blink?
Does the "ECONAVI Led" turn on and
5
"Quick Freezing" blinking?
Does the "ECONAVI Led" turn off and
6
"Quick Freezing" blink?
Does the "ECONAVI Led" turn off, "Quick
7
Freezing" turn off and "Freezer Control" LED
"MAX" blink?
Does the "ECONAVI Led" turn off, "Quick
8
Freezing" turn off and "Freezer Control" LED
"MIN" blink?
YES
YES
NO
NO
NO
NO
NO
NO
• Check power supply.
Ex. Connect power cord in inlet
Ex. Check ELCB
• Defect of over load relay.
Ex. Does fuse blow?
• Check control PCB.
Ex. Does fuse blow?
Ex. Defect of IC, Diode, etc.
• Defect of control PCB.
NO
• Defect PC door switch.
YES
• Defect of control PCB.
• Communication error
• Defect of control PCB.
YES
• Abnormal connecting of compressor.
• Compressor lock.
• Chock.
• Leakage.
• Droping voltage of power supply.
• Rising voltage of power supply.
• Break FC thermistor.
YES
• Poor connection between FC thermistor and
PCB.
• Gas leakage at high pressure side.
YES
• Poor compression.
• Defect of control PCB.
YES
• Gas leakage at low pressure side.
• Defect of control PCB.
• Faulty compressor motor.
• Compressor lock.
- 14 -