Installation
HP (KW)
UL Motor Current
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
75 (55)
100 (75K)
125 (90)
HP (KW)
UL Motor Current
15 (11)
20 (15)
25 (18.5)
30 (22)
40 (30)
50 (37)
60 (45)
75 (55)
100 (75)
125 (90)
Table 3.10 Wire Size Chart 460 and 600 V
3.4.4 Wire Type Rating
•
The wire style rating specifications are provided inTable 3.9 and Table 3.10
3.4.5 Terminal Tightening Torques
•
Tighten all connections to the torque specifications provided in Table 3.11 and Table 3.13
•
The torque specifications are also located on the tightening torque and wire rating label inside the panel cover.
See Table 3.15 for a sample of the torque and wire rating data.
3-20
Panel (TR200) Non Bypass
& Bypass
21
27
P2
34
40
52
P3
65
77
P4
96
124
P5
156
Panel (TR200) Non Bypass
& Bypass
17
22
P2
27
32
41
P3
52
62
P4
77
99
P5
125
460 VAC
Maximum Field
Wiring Size Class B
Wiring Size Class B
or C
10 AWG
8 AWG
6 AWG
6 AWG
4 AWG
3 AWG
1 AWG
1 AWG
2/0 AWG
3/0 AWG
600 VAC
Maximum Field
Wiring Size Class B
Wiring Size Class B
or C
10 AWG
10 AWG
8 AWG
8 AWG
6 AWG
4 AWG
3 AWG
1 AWG
1 AWG
2/0 AWG
Field Ground
Minimum Temperature
Wire Rating "°C" Copper
or C
Conductor
10 AWG
10 AWG
10 AWG
10 AWG
10 AWG
8 AWG
8 AWG
8 AWG
6 AWG
6 AWG
Field Ground
Minimum Temperature
Wire Rating "Degree C"
or C
Copper Conductor
10 AWG
10 AWG
10 AWG
10 AWG
10 AWG
10 AWG
8 AWG
8 AWG
8 AWG
6 AWG
BAS-SVX49A-EN
60
60
60
60
60
60
60
60
75
75
60
60
60
60
60
60
60
60
60
75