10. M-NET CONTROL

10-1. Address setting
10. M-NET CONTROL
10-1-1. Rule of setting address
Unit
Indoor unit
Outdoor unit
Hydro unit
HBC controller
ME Remote
controller
(Main)
ME Remote
controller
(Sub)
ON/OFF remote
controller
AE-200E/AE-50E
AG-150A
EW-50E
AT-50B
PAC-YG50ECA
BAC-HD150
LMAP04-E
PAC-YG60MCA
PAC-YG63MCA
PAC-YG66DCA
Lossnay, OA
processing unit
PAC-IF01AHC
Note1: To set the address to "100", set it to "50"
Note2: Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in
descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
MEES18K068
Address setting
Example
01 ~ 50
10
51 ~ 99, 100
(Note1)
10
52 ~ 99, 100
10
52 ~ 99, 100
10
1
101 ~ 150
Fixed
10
1
151 ~ 199, 200
Fixed
10
201 ~ 250
100
10
0,2
0~5
000, 201 ~ 250
100
10
0,2
0~5
000, 201 ~ 250
100
10
0,2
0~5
000, 201 ~ 250
100
10
2
201 ~ 250
Fixed
10
01 ~ 50
10
01 ~ 50
10
01 ~ 50
10
01 ~ 50
10
2
201 ~ 250
Fixed
10
Note
Use the most recent address within the same group of
indoor units.
1
The smallest address of indoor unit in same refrigerant
system + 50
Assign sequential address numbers to the outdoor
units in one refrigerant circuit system. OC, OS1 and
OS2 are automatically detected. (Note 2)
Please reset one of them to an address between 51
1
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The address of the smallest address of outdoor unit
connected to the hydro unit +50
Please reset one of them to an address between 52
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
1
as "01~ 50"
The address of the smallest address of indoor unit
connected to the HBC controller +50
Please reset one of them to an address between 52
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
1
as "01~ 50"
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
1
The address of main remote controller + 50
The address automatically becomes "200" if it is set
as "00"
1
The smallest group No. to be managed + 200
The smallest group No. to be managed is changeable.
1
0~9
AT-50B cannot be set to "000".
1
0~9
Settings are made on the initial screen of AG-150A.
1
0~9
Settings are made with setting tool of BM ADAPTER.
1
1
1
1
1
After setting the addresses of all the indoor units,
assign an arbitrary address.
1
1
R2-Series
72