5. SOUND LEVELS

5-2. Sound levels in heating mode

Measurement condition
PURY-M200, 250, 300YNW-A1(-BS)
Sound level of PURY-M200YNW-A1(-BS)
90
Stand 50/60Hz
Low
80
70
60
50
40
30
Approximate minimum
20
audible limit on
continuous noise
10
63
125
250
500
Octave band central frequency (Hz)
63
125
Standard Heating
50/60Hz 69.0 61.0 60.5 58.0 52.0 47.5
Low noise mode
50/60Hz 43.0 49.0 42.0 40.0 36.0 33.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
Sound level of PURY-M250YNW-A1(-BS)
90
Stand 50/60Hz
Low
80
70
60
50
40
30
Approximate minimum
20
audible limit on
continuous noise
10
63
125
250
500
Octave band central frequency (Hz)
63
125
Standard Heating
50/60Hz 69.0 62.5 62.0 60.0 54.0 49.5
Low noise mode
50/60Hz 47.5 51.5 46.0 44.5 40.5 37.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.
For HBC controller, it is recommended to be installed in places such as ceilings of corridor, rest rooms and plant rooms.
MEES18K068
1m
Measurement
location
50/60Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1k
2k
4k
8k
250
500
1k
2k
4k
8k
dB(A)
48.0
42.5
59.0
37.0
35.5
44.0
50/60Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1k
2k
4k
8k
250
500
1k
2k
4k
8k
dB(A)
50.5
44.0
61.0
41.0
37.5
48.0
Sound level of PURY-M300YNW-A1(-BS)
90
Stand 50/60Hz
Low
50/60Hz
80
70
60
50
40
30
Approximate minimum
20
audible limit on
continuous noise
10
63
125
250
500
Octave band central frequency (Hz)
63
125
250
Standard Heating
50/60Hz 74.5 70.0 68.5 65.5 60.5 56.5
Low noise mode
50/60Hz 60.5 58.0 50.0 47.5 43.0 39.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
R2-Series
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1k
2k
4k
8k
500
1k
2k
4k
8k
dB(A)
52.0
48.0
67.0
38.5
41.5
50.5
39