M-Net Control; 10-1.Transmission Cable Length Limitation - Mitsubishi Electric SMART MULTI MXZ-SM36NAM2-U1 Data Book

Hide thumbs Also See for SMART MULTI MXZ-SM36NAM2-U1:
Table of Contents

Advertisement

10. M-NET CONTROL

10-1. Transmission cable length limitation
10. M-NET CONTROL
10-1-1. Using MA Remote controller
MA remote controller refers to Simple MA remote controller and wireless remote controller.
Applicable to Outdoor as follows
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable)
MXZ-SM NAM(HZ)2-U1
Max. length to Outdoor (M-NET cable)
MXZ-SM TAM-U1
Max. length from MA to Indoor for each group
24VDC to AG-150A-A
OC
(51)
M1 M2 S
TB7
Shielded
wire
OC
(52)
TB7
M1 M2 S
Power Supply Unit
PAC-SC51KUA
A B
S
AG-150A-A
AE-200A
A B S
A B
S
10-1-2. Using ME Remote controller
ME remote controller refers to Smart ME controller.
Applicable to Outdoor as follows
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L1+L2+L3+L5, L3+L4+L6+L7, L3+L5+L6+L7, L4+L5 <=500m[1640ft] 1.25mm
MXZ-SM NAM(HZ)2-U1
Max. length to Outdoor (M-NET cable) L1, L3+L4, L2+L6, L7, L3+L5
MXZ-SM TAM-U1
Max. length from ME to Indoor
24VDC to AG-150A-A
*1. If the length from ME to Indoor exceed 10m, use 1.25 mm
OC
(51)
M1 M2 S
TB7
Shielded
wire
OC
(52)
TB7
M1 M2 S
Power Supply Unit
PAC-SC51KUA
A B S
AG-150A-A
AE-200A
A B S
A B
S
M-P0890
Group1
IC
(01)
TB3
TB5
TB15
M1 M2
M1 M2
S
1 2
A B
MA
IC
(02)
TB3
TB5
TB15
M1 M2
M1 M2 S
1 2
V+V-FG
V+V-FG
OC: Outdoor unit; IC: Indoor unit; MA: MA remote controller
e1,e2,e3,e4
n
Group1
IC
(01)
TB3
TB5
M1 M2
M1 M2 S
A B
(101)
ME
L
3
IC
(02)
TB3
TB5
M1 M2
M1 M2 S
V+V-FG
OC: Outdoor unit; IC: Indoor unit; ME: ME remote controller
V+V-FG
L1+L2+L3, L1+L2+L4+L5, L3+L4+L5
L1, L3, L2+L4, L5
a1+a2, a1+a2+a3+a4
n
L
1
Group3
IC
(04)
TB5
TB15
M1 M2 S
1 2
L
3
IC
(03)
TB 15
TB5
M1 M2 S
1 2
A B
MA
2
[AWG16] shielded cable, but the total length should be counted into Max. length via Outdoor.
L
1
Group3
IC
(04)
TB5
M1 M2 S
IC
(03)
TB5
M1 M2 S
A B
(103)
ME
SMART MULTI
2
<=500m[1640ft]
1.25mm
[AWG16] or thicker
2
<
2 =
0 0
m
6 [
6 5
] t f
1.25mm
[AWG16] or thicker
2
<=200m[656ft]
0.3-1.25 mm
[AWG22-16]
2
<=50m[164ft]
0.75-2.0 mm
[AWG18-14]
Group5
IC
(05)
TB5
TB15
M1 M2 S
1 2
a2
A B
MA
IC
(07)
TB5
TB15
M1 M2 S
1 2
A B
MA
NOTE
Do not daisy-chain remote controllers.
2
[AWG16] or thicker
2
<=200m[656ft] 1.25mm
[AWG16] or thicker
2
<=10m[32ft] *1 0.3-1.25 mm
2
<=50m[164ft]
0.75-2.0 mm
Group5
IC
(05)
TB5
M1 M2 S
A
B
A
(105)
(155)
ME
ME
L
4
IC
(07)
TB5
M1 M2 S
NOTE
Do not daisy-chain remote controllers.
IC
(06)
TB5
TB15
M1 M2 S
1 2
[AWG22-16] *1
[AWG18-14]
IC
(06)
TB5
M1 M2 S
B
53