9. ELECTRICAL WORK

9-1. Power supply for Outdoor unit

9. ELECTRICAL WORK
9-1-1. Electrical characteristics of the outdoor unit in cooling mode
PURY-M-YNW-A1
PURY-M200YNW-A1(-BS)
PURY-M250YNW-A1(-BS)
PURY-M300YNW-A1(-BS)
PURY-M350YNW-A1(-BS)
PURY-M400YNW-A1(-BS)
PURY-M450YNW-A1(-BS)
PURY-M500YNW-A1(-BS)
PURY-EM-YNW-A1
PURY-EM200YNW-A1(-BS)
PURY-EM250YNW-A1(-BS)
PURY-EM300YNW-A1(-BS)
PURY-EM350YNW-A1(-BS)
PURY-EM400YNW-A1(-BS)
PURY-EM450YNW-A1(-BS)
PURY-EM500YNW-A1(-BS)
MEES18K068
Units
Unit Combination
Hz
Volts
-
-
-
380
50/60
400
-
415
-
-
-
Units
Unit Combination
Hz
Volts
-
-
-
380
50/60
400
-
415
-
-
-
Symbols: MCA: Max Circuit Amps
RLA: Rated Load Amps
Power
Compressor
supply
Voltage
MCA
Output
SC
range
(A)
(kW)
(A)
16.1
4.6
8
22.5
7.0
8
25.6
8.0
8
Max:456V
31.6
9.6
8
Min:342V
39.3
12.2
8
40.2
13.1
8
56.6
17.4
8
Power
Compressor
supply
Voltage
MCA
Output
SC
range
(A)
(kW)
(A)
16.1
4.5
8
21.8
6.7
8
23.9
7.7
8
Max:456V
30.0
9.6
8
Min:342V
35.9
11.1
8
36.9
12.7
8
46.9
13.8
8
SC: Starting Current
FAN
RLA (A) (50/60Hz)
Output (kW)
Cooling
Heating
0.92
9.3/8.8/8.5
10.7/10.2/9.8
0.92
14.1/13.4/12.9 15.4/14.6/14.1
0.92
16.6/15.8/15.2 17.4/16.5/15.9
0.46+0.46 20.5/19.4/18.7 20.5/19.5/18.7
0.46+0.46 25.5/24.2/23.4 23.7/22.5/21.7
0.46+0.46 26.1/24.8/23.9 27.3/25.9/25.0
0.92+0.92 37.5/35.6/34.3 30.8/29.2/28.2
FAN
RLA (A) (50/60Hz)
Output (kW)
Cooling
Heating
0.92
8.6/8.2/7.9
10.5/9.9/9.6
0.92
12.9/12.3/11.8 14.9/14.1/13.6
0.92
14.3/13.6/13.1 16.7/15.9/15.3
0.46+0.46 19.1/18.1/17.5 20.5/19.5/18.7
0.46+0.46 23.3/22.1/21.3 23.4/22.2/21.4
0.46+0.46 25.7/24.4/23.5 26.6/25.2/24.3
0.92+0.92 30.4/28.9/27.9 29.4/27.9/26.9
R2-Series