Connecting PMI/PMI-2/PMI-3 A 40 inch long 60 wire cable, P/N 555-133743 (shipped with the PMI/PMI-2/PMI-3),
Connecting The Optional
HTSW-1 Tamper Switch
Connecting The
LCM/SCM/FCM
Connecting The
SSD-C-REM
POST-INSTALLATION
COMPATIBILITY
Siemens Industry, Inc.
Building Technologies Division
The RNI mounts on studs in the rear of either the REMBOX2 or the REMBOX4. Four
#8/32 nuts are provided with the RNI. (Refer to the REMBOX2/REMBOX4 Installation
Instructions, P/N 315-033772.) For Global PMI/PMI-2/PMI-3 applications the RNI can
also be installed in a CAB1/CAB2/CAB3 using mounting plate, RNI-CAB-BRKT, P/N
500-650062. (Refer to RNI-CAB-BRKT Installation Instructions, P/N 315-050062.)
Install the RNI with the terminal blocks facing up to allow for easier connection of the
field wiring.
connects the RNI to the PMI/PMI-2/PMI-3. Connect one end of the cable to JP1 on
the RNI and the other end of the cable to either JP3 on the PMI or J2 on the PMI-2/
PMI-3. Be sure that the PMI/PMI-2/PMI-3 address agrees with the ZEUS configura-
tion. Refer to the PMI Installation Instructions, P/N 315-033070, the PMI-2 Installation
Instructions, P/N 315-050636, or the PMI-3 Installation Instructions, Document ID
A6V10446194.
Connect the HTSW-1 (required for UL1076) to P6 on the RNI using the connector
supplied with HTSW-1. Refer to the REMBOX Installation Instructions, P/N 315-
033772 and the HTSW-1 Installation Instructions, P/N 315-033350.
Mount the LCM/SCM/FCM to the ID-MP (Refer to the LCM/SCM/FCM Installation
Instructions, P/N 315-033040). Mount the ID-MP to the inner door of the REMBOX2/4.
Mount the SSD-C-REM to the inner door of the REMBOX2/4. Using the 8-wire cable
supplied with the SSD-C-REM, connect the SSD-C-REM to P2 on the RNI.
Before applying power to the RNI check the following:
Ensure that the 24VDC power input on TB1 is connected and that the
polarity is correct.
Check the setting of S1. If the RNI is at the end of the HNET is must be set
to on. If the RNI is in the middle of the HNET/XNET it must be set to off. If
the HNET/XNET is not used the position of S1 does not matter.
Check the position of P5. It must be set to H for HNET or X for XNET.
Check the CAN termination. If the RNI is at the end of the CAN network, a
CAN terminator (P/N110-134215, supplied with the NIC-C) must be installed
into the last CAN module in the REMBOX.
If the RNI is in the middle of the CAN network no CAN terminators can be
installed. If CAN is not used then the terminator can be stored in P4. It will
be needed if CAN modules are added to the REMBOX at a later time. Refer
to the NIC-C Installation Instructions P/N 315-033240 for examples of CAN
installation and termination.
Check the setting of P7 . If the local sound is required, make sure P7 is set to
ON. Otherwise, set it to OFF .
The RNI is compatible with the FireFinder XLS HNET, XNET and CAN networks only.
The RNI can not be used with the MXL MNET.