Step Thermostat Processing (Fxtq-Ta Models) - Daikin REYQ-TA Series Service Manual

Heat recovery 60 hz
Table of Contents

Advertisement

SiUS371614E

9.13 3 Step Thermostat Processing (FXTQ-TA Models)

Outline
The thermostat ON/OFF for the indoor unit is controlled in accordance with [Thermostat Step 1].
The heater ON/OFF operation during heating is controlled as follows.
For more details of the heater, refer to Heater Control (FXTQ-TA Models) on page 107.
Detail
• Thermostat step 1: OFF
• Thermostat step 2: OFF
• Thermostat step 3: OFF
(1) Cooling
ON
Thermostat step 2
OFF
Thermostat step 1
ON
OFF
A (∗4)
Set temperature (Ts')
∗1. S value varies automatically based on the room temperature trend.
Note:
∗2. Ton + S > –B (°C), Toff + S < A (°C)
∗3. For parameters, refer to page 124.
∗4. A and B values vary automatically based on the field setting 12(22)-2.
∗5. If, directly after a change in conditions, it is such that the thermostat could be either ON or OFF
Functions and Control
Thermostat step 2, 3: Auxiliary electric heater control
Thermostat step 1, 2: Heat pump lockout control
• No errors (except errors in which the system keeps operating)
has occurred.
&
• Remote controller ON
Elimination conditions of the above
2+S (∗1)
4+S (∗1)
B (∗4)
Controlled temperature
(Tcon)(˚C)
(controlled temperature is within ranges A and B), the thermostat will be switched to ON.
Perform the processing in
the following chart. (∗5)
(2) Heating
Thermostat step 3
ON
1.5
OFF
Thermostat step 2
ON
Ton+S
OFF
(∗1,2,3)
ON
Thermostat step 1
OFF
Outline of Control (Indoor Unit)
1.5
Toff+S (∗1,2,3)
B (∗4)
A (∗4)
Controlled
temperature
Set temperature (Ts')
(Tcon)(˚C)
110