Daikin REYQ-TA Series Service Manual page 140

Heat recovery 60 hz
Table of Contents

Advertisement

Field Setting from Remote Controller
Compensating the Floor Temperature
(For units with the infrared presence/floor sensor only)
Offset the detected value of the infrared floor sensor with a certain temperature. This setting should be used to
have the actual floor temperature detected when, for example, the unit is installed close to a wall.
Mode No.
11 (21)
Actual procedure to use the setting
Although the standard setting is normally used with no problem, the setting should be changed in the following
cases:
· The unit is installed close to a wall or a window.
· High thermal capacity of the floor whose material is
concrete, etc.
· There are many heat sources like a PC.
· There is a non-negligible heat source such as floor
heating.
Optional Output Switching
Using this setting, "operation output signal" and "abnormal output signal" can be provided. Output signal is output
between terminals X1 and X2 of "adaptor for wiring", an optional accessory.
Mode No.
12 (22)
External ON/OFF Input
This input is used for "ON/OFF operation" and "Protection device input" from the outside. The input is performed
from the T1-T2 terminal of the operation terminal block in the electrical component box.
Mode No.
12 (22)
127
First Code No.
Second Code No.
9
Environment
First Code No.
Second Code No.
0
First Code No.
Second Code No.
1
01
02
03
04
Operation Mode
Heating
01
Indoor unit thermostat ON/OFF signal is provided.
02
Output linked with "Start/Stop" of remote controller is
03
provided.
In case of "Error Display" appears on the remote
04
controller, output is provided.
05
06
Only for FXMQ-PB
07
Economizer (field supply) ON/OFF signal is provided.
F2 T1 T2
Forced stop
Input A
ON: Forced stop (prohibition of using the remote
01
controller)
OFF: Permission of using the remote controller
OFF → ON: Permission of operation
02
ON → OFF: Stop
ON: Operation
OFF: The system stops, then the applicable unit
03
indicates A0. The other indoor units indicate
U9.
04
Only for FXMQ-PB
05
ON: Economizer (field supply) is connected.
OFF: Not connected
SiUS371614E
Contents
–4°C (–7.2°F)
–2°C (–3.6°F)
0°C (0°F)
+2°C (+3.6°F)
Problem
Setting Value
Heated too much
+2°C (+3.6°F)
–2°C or –4°C
Heated little
(–3.6°F or –7.2°F)
Contents
Contents
Field Settings