Daikin REYQ-TA Series Service Manual page 167

Heat recovery 60 hz
Table of Contents

Advertisement

SiUS371614E
Image of operation in the case of A and B
Power consumption
Rated power consumption
70 % of rated power
consumption
40 % of rated power
consumption
Forced thermostat OFF
(Fan operation)
Detailed Setting Procedure of Low Night Noise Operation and Demand Control
1. Setting mode 1 (H1P OFF)
In setting mode 2, press the BS1 (MODE button) once → Setting mode 1 is entered and H1P turns OFF.
During the setting mode 1 is displayed, "In low night noise operation" and "In demand control" are displayed.
2. Setting mode 2 (H1P ON)
(1) In setting 1, press and hold the BS1 (MODE button) for more than 5 seconds. → Setting mode 2 is entered
and H1P lights.
(2) Press the BS2 (SET button) several times and match the LED display with the Setting No. you want.
(3) Press the BS3 (RETURN button) once, and the present setting content is displayed.
→ Press the BS2 (SET button) several times and match the LED display with the setting content you want.
(4) Press the BS3 (RETURN button) two times. → Returns to (1).
(5) Press the BS1 (MODE button) once → Returns to the setting mode 1 and H1P turns OFF.
Field Settings
The power consumption set with
"Demand 1 level setting".
Demand level
Demand level
2 instructing
3 instructing
Field Setting from Outdoor Unit
The power
consumption can
be set with the
"Demand 1 level
setting". ("70 % of
rated power
consumption" has
been set at
factory.)
During continuous
demand operation, when
the external demand
instruction is received
repeatedly, the instruction
with higher demand level
has the precedence.
154