Special Control
[While in cooling/heating mixed mode, single-room heating → cooling]
First, the electronic expansion valve of the indoor unit in heating operation will close, and the Y2E and Y3E electronic
expansion valves of the branch selector unit will all close once.
Next, the Y3E electronic expansion valve will open little by little to perform pressure equalization.
Then the electronic expansion valve will fully open, and the electronic expansion valve of the indoor unit will open to
activate the heating circuit.
The required switching time is approximately 6 minutes. (Field settings, however, can shorten the time from 6 minutes to 4
minutes.)
(1) In heating
(2) In equalization
(3) To cooling