WIKA D-20-9 Operating Instructions Manual page 20

Pressure sensor canopen
Hide thumbs Also See for D-20-9:
Table of Contents

Advertisement

Available languages

Available languages

9. Specifications
Specifications
Accuracy
EN
Non-linearity
Non-repeatability
Long-term stability
Permissible temperature ranges
Medium
Ambient
Storage
Compensated temperature
range
Temperature coefficients in
the compensated temperature
range
Mean TC of zero point
Mean TC of span
Shock resistance
Vibration resistance
Electrical safety
20
≤ ±1 % of span
≤ ±0.5 % of span (option)
≤ ±0.3 % of span (option, not possible in combination with DIP switch)
Including non-linearity, hysteresis, zero offset and end value deviation (corresponds to measured
error per IEC 61298-2). Calibrated in vertical mounting position, process connection facing
downwards.
The existence of strong electromagnetic fields in a frequency range of < 2.7 GHz can result in
increased measuring errors up to 1 % of span. Do not install the instruments in the vicinity of
strong electromagnetic sources of interference (e.g. transmitting devices, radio equipment), or
use sheath current filters where applicable.
≤ ±0.2 % of span (BFSL) per IEC 61298-2
≤ 0.1 % of span
≤ ±0.2 % of span/year (at reference conditions)
-30 ... +100 °C
-40 ... +125 °C (option)
-20 ... +80 °C
-40 ... +100 °C
0 ... 80 °C
≤ 0.2 of span / 10 K
≤ 0.2 of span / 10 K
500 g to IEC 60068-2-27 (mechanical shock)
Version with DIP switch: 20 g per IEC 60068-2-6 (vibration under resonance)
Version without DIP switch: 10 g per IEC 60068-2-6 (vibration under resonance)
Reverse polarity protection UB+ to UB-
WIKA operating instructions, pressure sensor, models D-20-9, D-21-9