5. Commissioning, operation
Requirements for electrical connection
Cable diameter matches the cable bushing of the mating connector.
Cable gland and seals of the mating connector are correctly seated.
With cable outlets, no humidity can ingress at the cable end.
The IP ingress protection only applies when plugged in using mating connectors that have the appropriate IP
ingress protection.
Requirement for shielding and grounding
The instrument must be grounded via the process connection.
Use the instrument with shielded cable, and ground the shield on at least one end of the lead.
Pin assignment (per CiA-DR 303-1)
Circular connector M12 x 1 (5-pin)
WIKA operating instructions, pressure sensor, models D-20-9, D-21-9
Shield
UB+
UB-
CAN-High
CAN-Low
1
2
3
4
5
EN
11