Assembly and Installation

4
Assembly and Installation
Level tank by adjusting the leveling bolts under the
tank (Fig. 5).
4.1

Safety Requirements

TANK DAMAGE
When exceeding critical values.
ATTENTION!
One must adhere to the following
critical values for safe operation.
Critical Values
Temperature:
Heating water (boiler)
Domestic water (tank)
Operating pressure:
Heating water (boiler)*
Domestic water (tank)
*
In the overall system, it is necessary to install a boiler pressure
relief value, expansion tank and P and T valve for the tank.
We reserve the right to make any changes due to technical modifications!
Installation and Maintenance Instructions Logalux S 120 „US"• Issue 07/2001
230 °F
203 °F
87 psi
145 psi
Fig. 5
Adjusting tank leveling bolts (sample picture)