BERMAD K10 Installation, Operation And Maintenance Manual

BERMAD K10 Installation, Operation And Maintenance Manual

Kinetic (air / vacuum) air valve

Advertisement

Quick Links

Kinetic (Air / Vacuum)
Air Valve
Model K10
Installation, Operation and
Maintenance Manual (IOM)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the K10 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for BERMAD K10

  • Page 1 Kinetic (Air / Vacuum) Air Valve Model K10 Installation, Operation and Maintenance Manual (IOM)
  • Page 3: Table Of Contents

    Safety ................Page 2 Operational Data ............Page 3 Materials and Connections ..........Page 3 K10 (1", ¾") Parts List ........... Page 4 K10 (2") Parts List ............Page 5 Unpacking and post shipment inspection ...... Page 6 Site Preparation ............Page 6 Installation..............
  • Page 4: General

    General BERMAD K10 is a high quality Kinetic air valve for a variety of irrigation networks and operating conditions. It evacuates air during pipeline filling and enables large volume air intake in the event of network draining. With its advanced aerodynamic design and Kinetic...
  • Page 5: Operational Data

    Operational Data Pressure rating ISO PN10, ANSI / ASME 150 Operating pressure range 0.1-10 bar / 1.5-150 psi Operating temperature Water up to 60° / 140˚ Materials and Connections Body material Glass-reinforced plastic Inlet diameter DN20, DN25, DN50 (¾", 1" 2") Connections Threaded Male BSPT, NPT for ¾", 1"...
  • Page 6: K10 1", ¾" Parts List

    K10 1", ¾" Parts List Body (#2) Test Point (#7) Kinetic Seal (#4) Float (#3) O-Ring (#5) Spacer (#6) Base (#1)
  • Page 7: K10 2", Parts List

    K10 2", Parts List Body (#1) Test Point (#7) Kinetic Seal (#4) Float (#3) Stopper Disc (#2)
  • Page 8: Unpacking And Post Shipment Inspection

    Unpacking and post shipment inspection Make sure that till the actual installation the valve ■ remains dry and clean in its original package. Unpack the valve and make sure that all the wrapping ■ materials are removed. Before installation it is necessary to inspect that no ■...
  • Page 9: Installation

    The K10 air valve is not to be used in systems ■ containing high suspended solids; consider selecting other Bermad Air Valve models for such water type. Installation Typical Applications Main irrigation networks - Air relief and vacuum ■ prevention downstream of pumps, along supply lines and at elevations in main irrigation networks.
  • Page 10 Installation instructions Install the Air Valve as close as possible to the pipe, ■ at a high point of its circumference, in vertical position (within 5 degrees of vertical alignment) and with its inlet facing down. The diameter of the pipe connecting the Air Valve ■...
  • Page 11: Start-Up And First Operation

    Start-up and first operation Open the shutoff valve and verify that the Air Valve ■ connections are not leaking; if needed follow the troubleshooting instruction section of this document. Please note that at the first time the valve is filled up some water may exit through its outlet port.
  • Page 12: Inspection

    Pipeline Draining When a pipeline is drained, a negative differential pressure is created causing atmospheric air to push the float down. The kinetic orifice stays open and air enters the valve chamber, preventing vacuum formation in the pipeline. Inspection The valve does not require any specific maintenance, however a periodical inspection of the seals and flushing of the valve are recommended for removing debris and foreign objects.
  • Page 13: Troubleshooting

    Valve does not Verify that the operating pressure relief air or does not exceed the valve’s rated allow air intake working pressure. Check and remove foreign objects. Clean the valve’s internal parts, replace if necessary. Consult Bermad if the symptom continues.
  • Page 14: Disassembling And Reassembling The Valve 1", ¾

    Disassembling and Reassembling the valve 1", ¾" Disassembling the K10 ¾", 1” valve 1. Release the valve’s body (Part #2) by turning it counterclockwise, un-screw and remove it from the valve’s Base (Part #1). Make sure that the valve parts, seated within the cover do not fall out of the cover.
  • Page 15 Reassembling the K10 ¾", 1” valve 1. Insert the float with the Kinetic Seal on the conduit pin to its place within the valve-cover; make sure that the float freely falls downwards along the conduit pin. 2. Make sure that the valve’s basis O-ring (Part #5) is fully inserted to its groove within the basis.
  • Page 16: Disassembling And Reassembling The Valve (2")

    Disassembling and Reassembling the valve K10-2" Disassembling the K10 2” valve 1. Pull the Stopper Disc (Part #2) out of the valve-cover then pull out the float assembly (Part #3). 2. Inspect the float’s Kinetic Seal (Part #4) and the Float (Part #3) for wear and tear.
  • Page 17 Fig. M Fig. N Fig. P...
  • Page 18 The information herein is subject to change without notice. BERMAD shall not be held lia The information herein is subject to change without notice. BERMAD shall not be held liable for any errors. All rights reserved. © Copyright by BERMAD.

Table of Contents