Changing The Air Filter - Maico WR 310 Operating Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

UK | 16 Changing the air filter

16 Changing the air filter

Filter change display: Once the set filter
change interval has elapsed, a filter change
message appears on the screen  menu
Ventilation/System status.
The LED of the active ventilation level flashes
regularly on the simple control unit.
Information about previous filter changes is
stored in the menu Reports/Filter service life.
16.1 Filter change – filter service life
The manufacturer recommends the
i
.
following
Check the air filters (unit, external and room
filters) regularly, depending on the amount of
Select shorter change intervals if a lot
dirt.
of dust or dirt is produced. Change them as
required.
Only use original air filters.
● G4, M5 and F7 unit filters every 3 months
● External filters (optional) every 6 months
● Room filters (optional) every 2 months
16.2 Filter orders
Orders: Go to the Ventilation/Filter/
i
Action menu to order the right air filter
directly ex factory.
Querying filter service life: Go to
the Ventilation/Filter menu to view the
current remaining filter lives.
WS 310/410/320/470
WS 170
WS 160 Flat
Filter type
Unit filter G4
Pollen filter F7
External filter
Room filter
Active carbon filter
(optional)
58
Article no.
310/410
170
320/470
Flat
0092.0560 0093.0270
0092.0559 0093.0271
0092.0563 0093.0272
TRIO
Filter type
M5 exhaust air filter,
variant Q
M5 exhaust air filter,
variant L
F7 pollen filter,
variant Q and L
16.3 Changing G4, M5 and F7
– with filter change display –
An imminent filter change is displayed on a
main control unit – the Status display must
be activated under Basic settings. With the
simple control unit, the LED of ventilation
level II flashes regularly, at longer intervals.
Recommendation: Change all unit
i
filters at the same time.
1. Switch off ventilation unit, disconnect at
all poles from the power supply, secure
against being accidentally switched back
on and position a visible warning sign.
2. Removing front cover(s):
310/410 320/470
Tilt front plate forwards at the two top
corners (magnets [M]) and remove from
above. Remove filter cover [A].
Article no.
Trio
GVT 20000020
GVT 20000022
GVT 20000021
unit filters

Advertisement

Chapters

Table of Contents
loading

Table of Contents