8 Troubleshooting

8.1 Error Messages

Display
- 1999
(blinking!)
9999
(blinking!)
PErr
Exceeding or falling short of the measuring range includes the following events:
Sensor break / sensor short circuit
Measured value is not within the measuring range of the sensor
Display overflow
During the initialization of the device (all displays turned on, upper 7-segment-display is blinking), you cannot
press any key.
WALTHER Temperature Controller Bundle WTRB-x-x
Reason/cause
Displayed value falls under meas-
uring range
Displayed value exceeds measur-
ing range
Start of firing curve not possible
because actual value ≥ desired
value 1
Action
• Is the medium to be measured
within the measuring range (too
hot – too cold?)
• Check sensor for sensor break
or sensor short circuit
• Check connection of sensor and
the connecting clamps
• Check line
• Check if the connected sensor
matches the configured sensor
type
The firing curve can be started if
actual value < desired value 1