Parameters - Walther WTRB-24DC-3500 Operating Manual

Temperature controller bundle
Table of Contents

Advertisement

Rev. 1.0

7.2 Parameters

IMPORTANT
Certain parameter will not be shown, if the device does not have the respective equipment.
Please see the following table for the factory settings which are in bold print.
Parameterization (PArA)
Control parameters will be entered here.
PArA ->
Parameter
Proportional range
Pb1
Derivative time
Dt
Reset time
rt
Cycle time
Cy1
Contact distance
db
Switching differential
HyS1, HyS2 1
Operating point
y0
Output level limiting
y1, y2
The type of controller determines the display of parameters. For some parameters, the decimal places depend
upon the equipment of the device. Factory settings are shown in bold print.
WALTHER Temperature Controller Bundle WTRB-x-x
Value
Description
0...9999
Size of the proportional range: The larger the P-range, the smaller
the gain of the controller. For Pb = 0, there is no efficient controller
structure (same behavior as for limit value monitoring). For a steady
controller, Pb > 0 is required.
0 ...
Influences the differential portion of the controller output signal. The
80 ...
influence of the D-portion increases with an increasing derivative
9999 [s]
time.
0 = derivative time turned off (no D-portion)
0 ...
Influences the integral portion of the controller output signal. The
350
influence of the I-portion becomes smaller with an increasing reset
... 9999 [s]
time.
0 = reset time turned off (no I-portion)
0.0 ...
For a switching outlet, select the cycle time as follows: the energy
20.0 ...
supply for the process should be almost continuous, and at the same
999.9 [s]
time, the switching elements should not be overstrained.
0.0 ...
Distance between the two controlling contacts in a three-point con-
999.9
troller
0.0 ...
Switching differential for a switching controller with proportional
1.0 ...
range Pb = 0 (same behavior as for limit value monitoring)
999.9
-100 ...
Output level for P- and PD-controller (for x = w, then y = y0)
0 ...
+100
0 ...
y1: Maximum output level limiting
100 [%]
-100 ...
y2: Minimum output level limiting (only working for Pb > 0)
+100 [%]
Walther Systemtechnik GmbH – D 76726 Germersheim
Telefon: +49 (0)7274-7022-0 Telefax: +49 (0)7274-7022-91
http://www.walther-2000.de – info@walther-2000.de
Page 28 of 42