6.2.3 Technical Information for WSSR-24DC-12000
Main Features
Product or type of component
Number of channels
Number of mains phases
Additional Characteristics
Mounting bracket
Rated current [In]
Outlet voltage
Control circuit voltage
Setup and type of connection
Starting torque
Connections – clamps
Capacity unbalance
Insulation resistance
Local signaling
Minimum switch voltage
Maximum switch voltage
Inlet current limits
Solid shaft outlet type
Load current
Absolute maximum voltage
Surge current
Drop in voltage
Resistance
Leakage current
Reaction time
Overvoltage category
Width
Height
Depth
Product weight
WALTHER Temperature Controller Bundle WTRB-x-x
Solid-state relay
1
1 phase
Symmetrical DIN rail
12 [A]
1...60 [VDC]
4...32 [VDC]
1 S
Inlets : 0,5...0,8 [N]
Outlets : 0,5...0,8 [N]
Screw terminals : 1 x 0,3...1 x 1,5 [mm²],
(AWG 22...AWG 16) for inputs
Screw terminals : 1 x 0,3...1 x 2,5 [mm²],
(AWG 22-AWG 14) for outputs
<= 10 [pF] for inlet / outlet
1000 [MΩ] at 500 [VDC]
LED green for input status
4 [VDC] turn-on
1 [VDC] turn-off
9...11 [mA]
DC contactor / Mosfet outlet
0,0025...12 [A]
60 [V]
<= 100 [A] for 10 [ms]
<= 0,5 [V] turned on
0,045 [Ω] turned on
<= 0,1 [mA] turned off
0,6 [ms] turning on
0,3 [ms] turning off
III
18 [mm]
90,3 [mm]
83,7 [mm]
0,09 [kg]
Walther Systemtechnik GmbH – D 76726 Germersheim
Telefon: +49 (0)7274-7022-0 Telefax: +49 (0)7274-7022-91
http://www.walther-2000.de – info@walther-2000.de
Page 24 of 42
LOAD 1...60VDC/12A
1
2
11/13+
14
SSM1D212BD
A2
A1
4
3
INPUT 4...32VDC

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Walther WTRB-24DC-3500

This manual is also suitable for:

Wtrb-230ac-6000Wtrb-24dc-6000Wtrb-24dc-12000

Table of Contents