Supported Commands ................... 25 Connecting to the CLI through the serial interface ............. 26 Section 5 – Local Display ....................29 OLED Display ......................29 Menu Mode ......................30 OLED Menu Structure ....................31 Main Menu Selections .................... 31 SMARTZONE G5 USER MANUAL...
Page 3
Warranty and Regulatory Information................66 Warranty Information ....................66 Regulatory Information ....................66 Support and Other Resources ..................67 Accessing Panduit Support ..................67 Acronyms and Abbreviations ..................68 Documentation Feedback ..................... 71 Appendix A: CLI Commands ..................72 Appendix B: Firmware Update Procedure ..............80 USB Method ......................
Section 1 – System Overview Intelligent Network Controller The Panduit Monitored Input, Monitored & Switched, Monitored per Outlet, and Monitored & Switched per Outlet PDUs have an integral, hot swappable Intelligent Network Controller. The Intelligent Network Controller contains the OLED interface, control buttons, the USB, Ethernet, Serial and Sensor ports, and recessed Reset Button.
2. Using a CLI command to enable DHCP or set a static IP. 3. Verify access to the Web interface. The Ethernet LED on the PDU front panel provides communication status by color and display activity. The recessed Reset button restarts the PDU (see Figure 2 below). SMARTZONE G5 USER MANUAL...
3. Open the terminal emulation program (HyperTerminal or PuTTY) on the computer and select the serial port connection (such as COM1). 4. Set the communications port as follows: • Bits per second: 115200 • Data bits: 8 SMARTZONE G5 USER MANUAL...
• Username: admin • Password: 12345678 (or your new password) 6. The “Panduit>” prompt appears after you have logged in, ready to enter the CLI command. 7. To configure network settings, enter the appropriate “net” command and press Enter.
Page 11
9. To set a static IPv4 configuration, run: • net tcpip static x.x.x.x (ipaddress) x.x.x.x (netmask) x.x.x.x (gateway) • Example: net tcpip static 192.168.1.100 255.255.255.0 192.168.1.1 • Enter Y to confirm and the PDU’s Intelligent Network Controller will reboot. SMARTZONE G5 USER MANUAL...
Open a supported web browser and enter the IP address of the PDU. If username and password were configured during the Network Configuration Setup: enter the username and password in the appropriate fields. Press Login or Enter. SMARTZONE G5 USER MANUAL...
If username and password were NOT configured during the Network Configuration Setup, use the default username: admin and password: 12345678. For security purposes, change the password upon login. Introduction to the Web GUI Login Page Figure 4: Login Page SMARTZONE G5 USER MANUAL...
This icon lets you select a Language. There are seven languages available to choose from: English, Chinese, French, Italian, German, Spanish, Korean and Japanese. This icon provides the logs of the PDU which can be viewed and downloaded. SMARTZONE G5 USER MANUAL...
Page 15
You also can also click user guide and license to ask for help. This icon shows who is logged in (user or admin). Account passwords can be changed, and user accounts managed through this page. SMARTZONE G5 USER MANUAL...
Introduction to the Dashboard Power Summary Page Figure 6: Power Summary Page Outlet Monitoring Page Figure 7: Outlet Monitoring Page SMARTZONE G5 USER MANUAL...
SNMP Management Configuration Setup SNMP 1. Access the Web interface and login. 2. Under SNMP Managers, select SNMP General. The SNMP General page displays. Figure 10: SNMP Management 3. The SNMP General includes SNMP Access and Version. SMARTZONE G5 USER MANUAL...
Figure 11: SNMP General Setup SNMP Port 1. Access the Web interface and login. 2. Under SNMP Managers, select SNMP Port. The SNMP Port page displays. SMARTZONE G5 USER MANUAL...
3. In the SNMP V1/V2c panel, select the SNMP V1/V2c manager to configure. Select the pencil icon in the last column. Figure 14: Define SNMP V1/V2c User 4. The Edit panel pop up displaying the configurable options. Figure 15: Edit V1/2c Manager SMARTZONE G5 USER MANUAL...
3. In the SNMP V3 panel, select the SNMP V3 manager to configure. Select the pencil icon in the last column. Figure 16: SNMP V3 Manager 4. The Edit panel pop up displaying the configurable options. SMARTZONE G5 USER MANUAL...
• NoAuthNoPriv: No authentication and no privacy. This is the default. • AuthNoPriv: Authentication and no privacy. • AuthPriv: Authentication and privacy. 7. Enter a new unique password to be used for authentication 8. Select the desired authentication algorithm. • MD5 • SHA SMARTZONE G5 USER MANUAL...
Page 25
9. Enter a new unique key for privacy algorithm 10. Select the desired privacy algorithm • DES • AES-128 • AES-192 • AES-256 11. Click Enable and Save. SMARTZONE G5 USER MANUAL...
PDU help query • sys command: PDU system configure and setting • net command: PDU net application configure and setting • usr command: PDU user operation • dev command: PDU device setting • pwr command: PDU power setting SMARTZONE G5 USER MANUAL...
Using the optional RJ45-DB9 cable, connect the RJ-45 end to the port labeled “Serial+RS485-1” on the front panel of your PDU model. Connect the DB9 end of the cable to the serial connector on the computer. SMARTZONE G5 USER MANUAL...
3. Enter the IP address in the Host Name field. Select the connection type: SSH • For SSH, enter 22 in the Port field. 4. Select Open. 5. Enter your Username. Press Enter. 6. Enter your password. Press Enter. SMARTZONE G5 USER MANUAL...
Page 29
7. You are now logged into the SSH. Refer to the CLI Commands table below for available commands. NOTE: SSH connection is not available when serial connection is enabled. SMARTZONE G5 USER MANUAL...
PDU values. Current values are refreshed every ten seconds. The user cannot select a custom sequence of screens. The screensaver displays automatically after 30 seconds of inactivity from the start-up screen, a menu, or a submenu. Values are refreshed every five seconds. SMARTZONE G5 USER MANUAL...
LED Unit Status The LED will change colors depending on the state of the PDU. LED State Description Solid Green Normal Operation Solid Red Critical or Warning Alarm Flashing Orange No network connection SMARTZONE G5 USER MANUAL...
The PDU menu selection hierarchy consists of Setup, Alarms, Power, and Sensors. On the main menu, scroll down to highlight Setup. Press Select. Scroll down to select a submenu and press Select to display the submenu options. Press Menu to return to the previous menu. SMARTZONE G5 USER MANUAL...
Network. Press Select to enter the Network Submenu. Scroll down to highlight the selected option from the menu. Press Select to display the screens that display the IP address. Press Menu to return to the previous menu. SMARTZONE G5 USER MANUAL...
Firmware version. On the Setup menu, scroll down to highlight Device submenu. Press Select to enter the Device Submenu. Scroll down to the item you wish to display and press Select. Press Menu to return to the previous menu. SMARTZONE G5 USER MANUAL...
The Screen submenu allows you to customize settings for Contrast, Rotate, and Always on. On the Setup menu, scroll down to highlight Screen. Press Select to select the submenu. Press Menu to return to the previous menu. SMARTZONE G5 USER MANUAL...
Setup menu, scroll down to highlight Lang. Press Select to display the screens to select the submenu. After you select the values, press Select to set the values as displayed on the screen. Press Menu to return to the previous menu. SMARTZONE G5 USER MANUAL...
Note 2: If you are in USB mode and you want to exit USB mode, you must remove the USB drive before existing USB mode. Otherwise, the PDU will reset and re-enter USB mode. SMARTZONE G5 USER MANUAL...
The Alarms menu displays active alarms for the PDU. On the Main Menu, scroll down to highlight Alarms. Press Select to display the Alarm Screen. When you finish your review, press Menu to return to the main menu. SMARTZONE G5 USER MANUAL...
The Power menu manages device, phase, breaker and outlet. On the Main Menu, scroll down to highlight Power. Press Select. Scroll down to select a submenu and press Select to display the submenu options. Press Menu to return to the previous menu. Figure 31: Power Menu SMARTZONE G5 USER MANUAL...
Phase. Press Select to display the screens to set the values for the submenu. After you select the phase, press Select to display the values for that phase on the screen. Press Menu to return to the previous menu. SMARTZONE G5 USER MANUAL...
The Breaker submenu is to display power values for the breakers. Press Select to display the values of the first breaker. To go to the next breaker, Select next. Press Menu to return to the previous menu. SMARTZONE G5 USER MANUAL...
On the Power menu, scroll down to highlight Outlet. Press Select to display values for the first outlet. To go to the next outlet, Select next. Press Menu to return to the previous menu. SMARTZONE G5 USER MANUAL...
The Sensor menu is to display temperature, humidity, door switch, fluid leak etc. On the Main Menu, scroll down to highlight Sensor. Press Select. This will display the sensor data for the first sensor. To go to the next sensor, Select next. Press Menu to return to the previous menu. SMARTZONE G5 USER MANUAL...
By default, passwords must be between 8 and 32 characters. Figure 37: Changing Your Password 2. Click Change Password to complete the password change. After initial login, to change the password: 1. Go to User Name>Change Password. SMARTZONE G5 USER MANUAL...
Figure 38: After Login 2. The Change User Password window opens. Figure 39: Change User Password 3. Enter the old password and then new password twice to confirm. By default, passwords must be between 8 and 32 characters. SMARTZONE G5 USER MANUAL...
• Administrator Privileges • Read Only The Panduit PDU comes with a standard Administrator Privileges profile and a standard Read Only profile. The “Admin Role” is typically the system administrator and has the Administrator Privileges with full operating permissions. By default the User Role is a Read Only profile.
Page 49
4. Use the Roles tab to set full or read only privileges. 5. Select “Add User” to save the new user profile. Modify user profile: 1. Go to User Administration>Users. 2. Select the user name. 3. Select Edit. Make changes to the user profile. SMARTZONE G5 USER MANUAL...
2. Select the red X next to user name. Setting up the system for Radius Authentication 1. Go to User Settings > in the admin menu. Figure 41: User Settings 2. Go to Radius Configuration and click the edit pencil. SMARTZONE G5 USER MANUAL...
2. Select the LDAP Enable checkbox. 3. Use the drop-down menu to choose the Type of LDAP Server. Choose Microsoft Active Directory. 4. Enter an IP Address of the domain controller/Active Directory (AD) Server. i.e.: 192.168.1.101 (example) 5. Enter a Port. SMARTZONE G5 USER MANUAL...
9. In the Login Name Attribute field, enter sAMAccountName (typically) 10. In the User Entry Object Class field, enter person. With these LDAP settings configured, the Bind is complete. (see screen shot) Figure 43: LDAP Configuration SMARTZONE G5 USER MANUAL...
LDAP authentication is ready to use. To test this, just click save, then click on “LDAP Configuration” again and type an Active Directory user name/password into the test box. Click Test LDAP Configuration. If a box pops up with all green “SUCCEEDED” (no X’s), the LDAP is successfully configured. SMARTZONE G5 USER MANUAL...
1. Locate a CAT-5 cable. Connect one end of the cable to one PDU. Connect the other end of the cable to the other PDUs. See Figure 3 for the location on the front panel of each model type. SMARTZONE G5 USER MANUAL...
• Each PDU is separately connected to the expansion and main’s private communications network. • The two PDUs are connected with a data communications bus to allow PDUs to share user-defined information. • Each PDU acts like a main PDU to report PDU data to both networks. SMARTZONE G5 USER MANUAL...
5. In RNA mode, the default account username is ‘landlord’ and password is ‘12345678’. This account is configured for proper access and control in RNA mode. 6. To enable this account, login to the CLI with admin credentials. 7. Enter the command ‘dev daisy rna init’. SMARTZONE G5 USER MANUAL...
Page 58
8. The following message will appear to confirm the landlord account is enabled: SUCCESS. 9. RNA is now configured and enabled. SMARTZONE G5 USER MANUAL...
Section 8– Web GUI configuration G5 iPDU Outlet Power Sequence Setup 1. From the PDU GUI Home menu select Control & Manage. Figure 47:Control & Manage PDU 2. Select Outlet Control Enabled SMARTZONE G5 USER MANUAL...
4. In the Edit Outlet window enter the On-Delay time (0-7200 seconds) then select Save. Figure 50: One-Delay Time 5. Your Outlet Power Sequence has been set. SMARTZONE G5 USER MANUAL...
These are all vital aspects of maintaining an efficient-working data center atmosphere. Users and administrators to can monitor the status, view reports, and alarms of specific conditions in and around a PDU, and server rack. (Note, only SmartZone G5 type sensors work with the SmartZone G5 iPDU controller) The following sensors are available: •...
Page 64
All Panduit G5 PDUs have two physical sensor ports, and each PDU can collect a total of eight sensor measurements (or readings). For example, if a PDU has a Door Sensor and an Environmental Three Temperature + Humidity Sensor connected, both physical sensor ports are used with a total of five sensor measurements recorded.
4. Select Edit button to configure the desired sensors. 5. In the Edit dialog box, type value of up critical, up warning, low warning, and low critical. 6. Select Save to exit the sensor setup. Repeat this process for additional sensors. SMARTZONE G5 USER MANUAL...
Warranty and Regulatory Information Warranty Information (http://www.Panduit.com) Regulatory Information Safety and regulatory compliance For important safety, environmental, and regulatory information, see Safety and Compliance Information at the Panduit website (http://www.Panduit.com) SMARTZONE G5 USER MANUAL...
Support and Other Resources Accessing Panduit Support • For live assistance, go to the Panduit.com website • To access documentation and support services, go to the Panduit website. SMARTZONE G5 USER MANUAL...
Acronyms and Abbreviations Amps/Amperes Alternating Current Advanced Encyption Standard Command Line Interface Data Encyption Standard DHCP Dynamic Host Configuration Protocol Gigabyte Graphical User Interface Intelligent Network Controller Internet Protocol iPDU Intelligent Power Distrubition Unit SMARTZONE G5 USER MANUAL...
Page 70
Kilo-Volt-Ampere Kilowatts Kilowatt Hour Local Area Network Liquid-Crystal Display LDAP Lightweight Directory Access Protocol OLED Organic Light-Emitting Diode Power Distribution Unit Quad-Network Interface Redundant Network Interface Secure Hash Algorithms SNMP Simple Network Management Protocol SMARTZONE G5 USER MANUAL...
Page 71
TCP/IP Transmission Control Protocol/Internet Protocol Universal Serial Bus Volts Watts SMARTZONE G5 USER MANUAL...
Documentation Feedback Panduit is committed to providing documentation that meets your needs. To help us improve the documentation, send any errors, suggestions, or comments to Documentation Feedback (CS@Panduit.com). When submitting your feedback, include the document title, part number, edition, and publication date located on the front cover of the document.
Panduit>sys time time. Panduit>sys time 14:35:34 sys ntp <IP Address> Synchronize system date >sys ntp 69.25.96.13 and time, with ntp server NOTE: IP Address must be a you set. valid ntp, server address otherwise, executes, failed SMARTZONE G5 USER MANUAL...
Page 74
NOTE 2: If in daisy chain configuration, master will also upgrade its all slave’s firmware. sys upd boot Update system’s Panduit>sys upd boot bootloader. SUCCESS system will enter upgrade mode after reboot System Reboot now, Are you sure?(Y/N):Y SMARTZONE G5 USER MANUAL...
Page 75
Delete data log file. Panduit>sys log del data, SUCCESS Panduit> Network Commands Command Description Example net ssh [on/off] Query or on/off SSH. Panduit>net ssh SUCCESS, SSH Port: 22 SSH Server is running SMARTZONE G5 USER MANUAL...
Page 76
Set network to dhcp mode. Panduit>net tcpip dhcp SUCCESS Network is reconfigured, Please reboot to validate System Reboot now, Are you sure?(Y/N): Y net tcpip <static ip, mask, Set static IP, mask and Panduit>net tcpip static gateway> gateway. 192.168.30.39 255.255.255.0 SMARTZONE G5 USER MANUAL...
Page 77
“Maximum number of failed logins”. Use this command to unlock it. Device Commands Command Description Example dev usb [on|off] Query or on/off USB. Panduit>dev usb Panduit>dev usb off Panduit>dev usb on SMARTZONE G5 USER MANUAL...
Page 78
1; if in daisy chain, the master's PDUID is 1, others is ,2,3, dev outlet <PDUID> Query or set specified Panduit> dev outlet 1 1 off <outlet index> [on|off] PDUID and outlet-index's SUCCESS outlet status. SMARTZONE G5 USER MANUAL...
Page 79
SKU: P9S20A , , , , unit’s electric information. Serial: , , , , , FuncType: PDU Monitored Rating :220-240V, 16A, 3.5-3.8kVA, 50/60Hz Mac :C8:45:44:66:2B:26 Tcpip :192:168:30:38 Panduit>pwr unit 1 SUCCESS PDU UNIT 1 power Feature SMARTZONE G5 USER MANUAL...
Page 80
<idx> Query specified outlet’s Panduit> pwr outlet 1 electric information. SUCCESS PDU OUTLET 1 power Feature voltage: 0V current : 0.0A active power: 0W apparent power: 0W NOTE: For Monitored PDUs, this command is invalid. SMARTZONE G5 USER MANUAL...
1. Open the User interface in a web browser by entering the PDU IP address. 2. Login to with Administration credentials. 3. Go to System Management >Update Firmware. 4. In the Firmware Update dialog box, browse to Panduit.FW firmware file. SMARTZONE G5 USER MANUAL...
Figure 54: Upload Firmware NOTE: the firmware file must be named Panduit.FW. 5. Select Upload. The system will update the newest firmware to the Intelligent Network Controller. SMARTZONE G5 USER MANUAL...
1. Login to a FTPs program with a role with administration privileges. 2. Transfer the updated Panduit.fw file to the folder labeled fw. Close the FTPs. 3. Connect to the PDU via SSH using a program such as HyperTerm or PuTTY.
Bootloader Mode 1. Go to www.Panduit.com and download the most recent Firmware version, ‘Panduit.bin’. Save this file to a USB drive. 2. Insert the USB drive into the USB port of the Intelligent Network Controller.
2. Select the Enable USB Access Checkbox. To upload configuration, you must: Copy conf.ini to USB. Insert USB to PDU. Enter USB mode in OLED device. Select Conf up. After the operation is completed, remove USB, and quit USB mode. SMARTZONE G5 USER MANUAL...
Circuit Breaker Status ON Circuit Breaker Status OFF Outlet X Active Power Above upper critical Outlet X Active Power Above upper warning Outlet Outlet X Active Power Below lower warning Outlet X Active Power Below lower critical SMARTZONE G5 USER MANUAL...
Page 87
System Communication Lost Daisy Chain state changed USB Port User Activity User X Authentication failure User Activity User X User logged in User Activity User Activity User X Session timeout User Activity User X User blocked SMARTZONE G5 USER MANUAL...
The circuit breaker (1-12) current is ABOVE critical threshold value 27-38 The circuit breaker (1-12) current is BELOW critical threshold value 39-50 The circuit breaker (1-12) is in OFF state 51-98 The outlet (1-48) active power is ABOVE critical threshold value SMARTZONE G5 USER MANUAL...
Page 89
The phase (1-3) voltage is BELOW warning threshold value. 208-210 The phase (1-3) current is ABOVE warning threshold value. 211-213 The phase 1 current is BELOW warning threshold value. 214-225 The circuit breaker (1-12) current is ABOVE warning threshold value. SMARTZONE G5 USER MANUAL...
Page 90
The outlet (1-48) DELAYED OFF occurred. 584-631 The outlet (1-48) IMMEDIATE REBOOT occurred. 632-679 The outlet (1-48) DELAYED REBOOT occurred. 680-727 The outlet (1-48) Cancel Pending Commands occurred. 728-735 The sensor (1-8) contact state is in cleared. Event log Cleared. SMARTZONE G5 USER MANUAL...
Page 91
User xxx password changed. User password settings changed. User xxx added. User xxx deleted. User xxx modified. Smart Rack Access Door Opened Smart Rack Access Door Closed Smart Rack Access User Card Swiped Smart Rack Access Door Autolocked SMARTZONE G5 USER MANUAL...
Page 92
The phase (1-3) voltage alarm cleared 774-776 The phase (1-3) current alarm cleared 777-788 The circuit breaker (1-12) current alarm cleared 789-836 The outlet (1-48) active power current alarm cleared. 837-844 The sensor (1-8) temperature/humidity alarm cleared. SMARTZONE G5 USER MANUAL...
Appendix E: Horizontal Intelligent Network Controller Replacement 1. Unscrew the left and right captive nuts on the Intelligent Network Controller by turning them counter clockwise. Figure 56: Unscrew Intelligent Network Controller SMARTZONE G5 USER MANUAL...
3. Insert the new Intelligent Network Controller. Figure 58: Inserting New Intelligent Network Controller 4. Align the Intelligent Network Controller and tighten the captive nuts by turning them clockwise. SMARTZONE G5 USER MANUAL...
Appendix F: Vertical Intelligent Network Controller Replacement 1. Use a T10 Torx screwdriver to remove the top and bottom screws from the Intelligent Network Controller. Figure 59: Removing Top and Bottom Screw from Intelligent Network Controller SMARTZONE G5 USER MANUAL...
Connect the signal wire to the new Intelligent Network Controller. Signal wire Figure 60: Disconnecting and Reconnecting the Intelligent Network Controller 3. Replace and tighten the two screws on the replacement Intelligent Network Controller into the PDU. SMARTZONE G5 USER MANUAL...