Condensate Trap Assembly - Installation - IBC DC Series Installation And Operating Instructions Manual

Boilers / water heaters
Hide thumbs Also See for DC Series:
Table of Contents

Advertisement

Figure 18: Condensate trap installation
NOTE
It is the responsibility of
the installing and/or service
Contractor to advise and
instruct the end User in how
to perform the Trap cleaning
procedure, and to advise
that the Trap be checked at
least every two months and
cleaned as required.
INSTALLATION
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
1.5.1 Condensate Trap
A condensate trap must be installed on the drain connection at the base of the
boiler / water heater as shown in Figure 18.

1.5.2 Condensate Trap Assembly - Installation

Undo Drain Spout Compression Nut, remove Drain Hose from Trap Drain
1.
Outlet. Remove Upper Compression Nut and Washer and slide over Boiler
/ Water Heater Drain Outlet (A). Insert one Trap Hook barb into the back
mounting hole.
Fill Trap with water, and slide Trap Body over Boiler / Water Heater Drain
2.
Outlet (A). Swing Trap Hook (B) around the Drain Outlet connection threads.
Insert remaining Trap Hook barb into the front hole. Pull the trap slightly
downward to seat it against the hook and tighten Upper Compression nut.
3.
Attach Drain Hose and tighten Drain Spout Compression Nut.
1-17