Seneca K109S Installation Manual

Seneca K109S Installation Manual

V - ma converter with 4-point galvanic insulation and auxiliary supply

Advertisement

Quick Links

EN
K109S

General Description

The K109S instrument is a V - mA converter with 4-point galvanic insulation designed for
industrial standard voltage or current signals with passive input, active output and
auxiliary supply.
Analog/digital conversion takes place at 14 bit on every input range.
The instrument also provides the following functions:
Auxiliary Supply, completely floating, isolated from the other ports, with voltage unrelated
to the input power supply.
Current or voltage input.
Programmable rejection for 50 or 60 Hz mains frequency.
Additional reading stabilisation filter.
Inversion of the input and inverted output scales
Input Out-of-Range programmable to 2.5% or 5.0%
SQRT function.
Linearisation for horizontal cylindrical tanks.
The module is also characterised by its extremely compact size, coupling to 35 mm DIN
rail, power supply available by bus, quick fit couplings by spring-type terminals, onsite
configuration by DIP-switch.

Technical Features

Power Supply :
Consumtion :
Dissipation :
Voltage Input :
Current Input:
Permissible max. Input Out-of-
Range:
Voltage Output :
Current Output :
Permissible max. Output Out-of-
Range :
Current output protection :
Auxiliary Supply:
Processing :
ADC :
V - mA CONVERTER
WITH 4-POINT GALVANIC INSULATION AND
AUXILIARY SUPPLY
19,2..30 Vdc
-max 23 mA at 24 Vdc ( with output at 20 mA and
auxiliary supply not used)
-max 45 mA at 24 Vdc ( with output at 21 mA
and auxiliary supply at 21 mA )
< 500 mW.
0..10 V, 2..10 V, 0..5 V, 1..5 V, Input Impedance :
110 k
0..20 mA, 4..20 mA, Input Impedance : 35
± 2,5 o ± 5% depending on settings (see section
Inputs-Outputs Limits)
0..5 Vdc, 1..5 Vdc, 0..10 Vdc e 2..10 Vdc
Minima load resistance di carico 2 K
0..20 mA, 4..20 mA, 20..0 mA, 20..4 mA
Maximum load resistance 500
Fixed (see section
approximately 25 mA
Voltage: 17..21 Vdc
Current: 0..25 mA.
Digital, 32 bit floating-point calculation
14 bit on every input range
MI00102 -E
4
Input-Output Limits
ENGLISH - 1/8
)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the K109S and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Seneca K109S

  • Page 1: General Description

    WITH 4-POINT GALVANIC INSULATION AND AUXILIARY SUPPLY General Description The K109S instrument is a V - mA converter with 4-point galvanic insulation designed for industrial standard voltage or current signals with passive input, active output and auxiliary supply. Analog/digital conversion takes place at 14 bit on every input range.
  • Page 2 10-90% response : 50 Hz : max 41 ms without filter and 88 ms with filter; 60 Hz : max 35 ms without filter and 74 ms with filter. Transmission : Digital Optical Max. transmission error 0.08% of the f.s. value for mA or 5 V output 0.07% of the f.s.
  • Page 3 Installation rules This module has been designed for assembly on a DIN 46277 rail. Assembly in vertical position is recommended in order to increase the module's ventilation, and no raceways or other objects that compromise aeration must be positioned in the vicinity. Do not position the module above equipment that generates heat;...
  • Page 4: Factory Setting

    SETTING OF THE DIP-SWITCHES Factory setting All the module DIP switches are at pos. 0 as defaut configuration. This set correspond to the following configuration : Input signal 0..20 mA 50-60 Hz mains frequency rejection 50 Hz Input filter Present Inversion Linearisation None...
  • Page 5 FUNCTION Default None SQRT Tank OUTPUT SIGNAL 0..20 mA 4..20 mA 20..0 mA 20..4 mA 0..10 Vdc 0..5 Vdc 1..5 Vdc 2..10 Vdc These are inverse output ranges that are useful whenever the linearisation applied is incompatible with the inversion of the input. INPUT OUT-OF-RANGE 2.5% Input Output Limits...
  • Page 6: Electrical Connections

    Electrical Connections The module has been designed for spring-type terminal electrical connections. Proceed as follows to make the connections: 1 - Strip the cables by 0.8 mm 2 - Insert a screwdriver in the square hole and press it until the cable lock spring opens. 3 - Insert the cable in the round hole.
  • Page 7 Input and Auxiliary Power Supply Input The module accepts a current or voltage input signal. The use of shield cables is recommended for the electronic connections. Voltage input Terminal 3: Voltage input. Terminal 4: Return (GND). Current input Terminal 3: Current input. Terminal 4: Return (GND) Auxiliary Power Supply The value of the provided voltage is indipendent from the one supplyed through 7 and 8...
  • Page 8 This document is property of SENECA srl. Duplication and reprodution are forbidden, if not authorized. Contents of the present documentation refers to products and technologies described in it. All technical data contained in the document may be modified without prior notice Content of this documentation is subject to periodical revision.

Table of Contents