Connecting
4.2 Interconnection
4.2.3
XPP-5 with IMA (internally mounted pre-amplifier)
XPP-5 cable must be run in dedicated, approved metal conduit, boxes and fittings and to
procedures in accordance with all governing regulations. See Cable length from RMA or IMA
to MFA 4p (Page 16) for cable lengths from probe at MFA 4p.
Note
Refer to Interconnection Diagram for XPP-5 (Page 17)
4.2.4
Cable length from RMA or IMA to MFA 4p
Wire gauge
22 AWG (0.34 mm
)
2
18 AWG (0.75 mm
)
2
12 AWG (4 mm
)
2
16
Length in feet
2 500
5 000
25 000
Length in meters
760
1 520
7 600