INSTALLATION OF DRAIN PIPE

• The diameter of the drain pipe should be larger than or equal
to that of the refrigerant pipe. (PVC pipe, outer diameter: 1 in.
(25 mm), wall thickness ≥ 1/16 in. (1.5 mm)).
• The drain pipe should be as short as possible and have a slope
of 1/100 degree minimum to avoid air pockets formation.
• If the installation do not allow proper drain pipe slope, a lift
pipe should be installed.
• A distance of 3.3 to 4.9 ft. (1 to 1.5 m) should be kept between
the hangers to avoid curves in the drain hose.
• Insert the drain hose into the drain hole and tighten it with
clamps.
• Wrap the clamps with a large amount of sponge for thermal
insulation.
• The drain hose inside the room should also be insulated.
Clamp (accessory)
Sponge (gray)
Drain Hose

PRECAUTIONS FOR LIFT PIPE

• The installation height of the lift pipe should be less than 11 in. (280 mm).
• The lift pipe should form a right angle with the unit, and distance to the unit should not exceed
11 13/16 in. (300 mm).
Drain hose
(accessory)
Ceiling
NOTES:
• The inclination height of the drain hose
should be within 3 in. (75 mm) so that
the outlet of the drain hose does not
suffer from external force.
20
Sponge (accessory)
Clamp
(accessory)
Max. 4 mm
Roof
3.3-4.9'
≤11 13/16"
(1-1.5 m)
(300 mm)
Clamp (accessory)
Drain hose
(attachment)
3.3-4.9'
(1-1.5 m)
With a min. degree
of slope 1/100
Hanger bracket
≤11"
(280 mm)
≤19 11/16"
(500 mm)
8 11/16"
(220 mm)
≤19 11/16"
(500 mm)
≤3"
(75 mm)