Circuit Diagram Inside The Terminal Box Cover; Direction Of Rotation; Knockout Openings - Siemens SIMOTICS XP 1MB1 series Operating Instructions Manual

Low-voltage motors
Hide thumbs Also See for SIMOTICS XP 1MB1 series:
Table of Contents

Advertisement

6.2.1.2

Circuit diagram inside the terminal box cover

Data on the connection and connecting the machine winding can be found in the circuit
diagram in the cover of the terminal box.
6.2.1.3

Direction of rotation

The standard motors are suitable for clockwise and counter-clockwise rotation.
For defined directions of rotation (direction of rotation arrow), appropriately connect the line
power cables.
● If you connect the line cables with phase sequence L1, L2, L3 at U, V, W or according to
NEMA at T
● If you interchange two connections, e.g. L1, L2, L3 at V, U, W or according to NEMA at
T
Clockwise rotation
Counter-clockwise
rotation
Direction of rotation of the motor when looking at DE
6.2.1.4

Knockout openings

NOTICE
Damage to the terminal box
To avoid damaging the terminal box:
• Knockout openings in the terminal box must be knocked out using appropriate methods.
• Do not damage the terminal box, the terminal board, the cable connections etc. inside
1LA5/6/7/9, 1LG4/6, 1MA6/7, 1MB..1/2/3/4/5 - SH 63 ... 355
Operating Instructions, 06/2018, A5E44455710A
T
T
, then the machine rotates in the clockwise direction.
1
2
3
T
T
, then the machine rotates counter-clockwise.
2
1
3
the terminal box.
According to IEC
U V W
V U W
Electrical connection
6.2 Connecting the machine
According to NEMA
T
T
T
1
2
3
T
T
T
2
1
3
71