Switch S2; Table 8: Dip Switch S2 Settings - Bosch FPP-RNAC-8A-4C Operation And Installation Manual

Remote nac power supply
Table of Contents

Advertisement

FPP-RNAC-8A-4C | Operation and Installation Guide | 4.0
4.2

Switch S2

Use Switch S2 to set the following (refer to Table 8):
NAC output control
AC failure delay time – 0, 1, 3, and 6 hour delay
Option bus address – Bus Addresses 1 to 14

Table 8: DIP Switch S2 Settings

Position Name
Position Number
NAC Output Control Options
NAC Input 1 controls
NAC Outputs 1 and 2.
NAC Input 2 controls
NAC Outputs 3 and 4.
NAC Input 1 controls all
four NAC Outputs
AC Failure Delay Reporting Options
No delay in AC failure reporting; the
unit signals an AC Failure
immediately.
AC failure reporting delay = 1 hour.
AC failure reporting delay = 3 hours
AC failure reporting delay = 6 hours
18
CNTRL
ALL/
AC
AC
CNTRL 2
DELAY 1
DELAY 0
0
1
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
Option Bus Settings
Disabled
Address 1
Address 2
Address 3
Address 4
Address 5
Address 6
Address 7
Address 8
Address 9
Address 10
Address 11
Address 12
Address 13
Address 14
Address 15
OPTION
OPTION
ADDRESS 4
ADDRESS 3
2
3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
Reserved
Bosch Security Systems, Inc. | 8/09 | F01U025431-02
DIP Switch and Option Bus Settings
OPTION
OPTION
ADDRESS 2
ADDRESS 1
4
5
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents